Toshiba GRL150-100 Series Instruction Manual page 207

Line differential relay
Table of Contents

Advertisement

Range
No.
Name
5A rating
76
EF
EF1
0.1 - 25.0
0.00 - 300.00
77
TEF1
78
TEF1M
0.010 - 1.500
79
TEF1R
0.0 - 300.0
0.010 - 1.500
80
TEF1RM
81
EF2
0.1 - 25.0
0.00 - 300.00
82
TEF2
83
EF3
0.1 - 250.0
0.02 - 50.00
84
TEF3
0.00 - 300.00
85
EF4
0.1 - 250.0
0.02 - 50.00
86
TEF4
0.00 - 300.00
87
EF1-k
0.00 - 300.00
88
EF1-α
0.00 - 5.00
89
EF1-C
0.000 - 5.000
90
EF1-kr
0.00 - 300.00
91
EF1-β
0.00 - 5.00
92
SEF
SE1
0.01 - 1.00
0.002 - 0.200
0.00 - 300.00
93
TSE1
94
TSE1M
0.010 - 1.500
95
TSE1R
0.0 - 300.0
0.010 - 1.500
96
TSE1RM
96
TS1S2
0.00-300.00
97
SE2
0.01 - 1.00
0.002 - 0.200
0.00 - 300.00
98
TSE2
99
SE3
0.01 - 1.00
0.002 - 0.200
100
TSE3
0.00 - 300.00
101
SE4
0.01 - 1.00
0.002 - 0.200
102
TSE4
0.00 - 300.00
103
SE1-k
0.00 - 300.00
104
SE1-α
0.00 - 5.00
105
SE1-C
0.000 - 5.000
106
SE1-kr
0.00 - 300.00
107
SE1-β
0.00 - 5.00
108
UC
UC1
0.5 - 10.0
109
TUC1
0.00 - 300.00
110
UC2
0.5 - 10.0
111
TUC2
0.00 - 300.00
112 Thermal
THM
2.0 - 10.0
113
THMIP
0.0 - 5.0
114
TTHM
0.5 - 500.0
115
THMA
50 - 99
116 BCD
BCD
0.10 - 1.00
117
TBCD
0.00 - 300.00
118
CBF
CBF
0.5 - 10.0
119
TBTC
0.00 - 300.00
120
TRTC
0.00 - 300.00
121 CLP/ICD
OC1
0.1 - 25.0
122
OC2
0.1 - 25.0
123
OC3
0.1 - 250.0
0.02 - 50.00
124
OC4
0.1 - 250.0
0.02 - 50.00
125
OC5
0.1 - 250.0
0.02 - 50.00
126
EF1
0.1 - 25.0
127
EF2
0.1 - 25.0
128
EF3
0.1 - 250.0
0.02 - 50.00
129
EF4
0.1 - 250.0
0.02 - 50.00
130
SE1
0.01 - 1.00
0.002 - 0.200
131
SE2
0.01 - 1.00
0.002 - 0.200
132
SE3
0.01 - 1.00
0.002 - 0.200
133
SE4
0.01 - 1.00
0.002 - 0.200
134
BCD
0.10 - 1.00
135
TCLE
0 - 10000
136
TCLR
0 - 10000
137
ICLDO
0.5 - 10.0
138
TCLDO
0.00 - 100.00
139
ICD-2f
10 - 50
140
ICDOC
0.5 - 25.0
Contents
Units
1A rating
0.02 - 5.00
A
EF1 Threshold setting (if EF1EN=On)
s
EF1 Definite time setting. (if MEF1=DT)
--
EF1 Time multiplier setting (if MEF1=IEC,IEEE,US)
s
EF1 Definite time reset delay (if EF1R =DEF)
--
EF1 Dependent time reset time multiplier (if EF1R=DEP)
0.02 - 5.00
A
EF2 Threshold setting (if EF2EN=On)
s
EF2 Definite time setting.(if MEF2=DT)
A
EF3 Threshold setting (if EF3EN=On)
s
EF3 Definite time setting.(if EF3EN=On)
A
EF4 Threshold setting (if EF4EN=On)
s
EF4 Definite time setting.(if EF4EN=On)
--
Configurable IDMT Curve setting of EF1.
--
ditto
--
ditto
--
ditto
--
ditto
A
SEF1 Threshold setting (if SE1EN=On)
s
SEF1 Definite time setting.(if MSE1=DT)
--
SEF1 Time multiplier setting (if MSE1=IEC,IEEE,US)
s
SEF1 Definite time reset delay (if SE1R =DEF)
--
SEF1 Dependent time reset time multiplier (if SE1R=DEP)
s
SEF1 Stage 2 definite timer settings (if SE1EN=On and SE1S2=On)
A
SEF2 Threshold setting (if SE2EN=On)
s
SEF2 Definite time setting.(if MSE2=DT)
A
SEF3 Threshold setting (if SE3EN=On)
s
SEF3 Definite time setting (if SE3EN=On)
A
SEF4 Threshold setting (if SE4EN=On)
s
SEF4 Definite time setting.(if SE4EN=On)
--
Configurable IDMT Curve setting of SEF1.
--
ditto
--
ditto
--
ditto
--
ditto
0.10 - 2.00
A
UC1 Threshold setting (if UC1EN=On)
s
UC1 Definite time setting (if UC1EN=On)
0.10 - 2.00
A
UC2 Threshold setting (if UC2EN=On)
s
UC2 Definite time setting (if UC2EN=On)
0.40 - 2.00
A
Thermal overload setting (if OLTEN=On)
0.00 - 1.00
A
Pre Current value (if OLTEN=On)
min Thermal Time Constant (if OLTEN=On)
% Thermal alarm setting (if OLTEN =On & ALTEN=On)
--
Broken Conductor Threshold setting (if BCDEN=On)
s
Broken Conductor Definite time setting. (if BCDEN=On)
0.10 - 2.00
A
CBF Threshold setting (if CBFEN=On)
s
Back trip Definite time setting
s
Re-trip Definite time setting
0.02 - 5.00
A
OC1 Threshold setting in CLP mode.
0.02 - 5.00
A
OC2 Threshold setting in CLP mode.
A
OC3 Threshold setting in CLP mode.
A
OC4 Threshold setting in CLP mode.
A
OC5 Threshold setting in CLP mode.
0.02 - 5.00
A
EF1 Threshold setting in CLP mode.
0.02 - 5.00
A
EF2 Threshold setting in CLP mode.
A
EF3 Threshold setting in CLP mode.
A
EF4 Threshold setting in CLP mode.
A
SEF1 Threshold setting in CLP mode.
A
SEF2 Threshold setting in CLP mode.
A
SEF3 Threshold setting in CLP mode.
A
SEF4 Threshold setting in CLP mode.
--
Broken Conductor Threshold setting in CLP mode.
s
Cold load enable timer (if CLEN=On)
s
Cold load reset timer (if CLEN=On)
0.10 - 2.00
A
Cold load drop-out threshold setting (if CLDOEN=On)
s
Cold load drop-out timer (if CLDOEN=1)
% Sensitivity of 2f
0.10 - 5.00
A
Threshold of fundamental current
Default Setting of Relay Series(5A rating / 1A rating)
Model1
100
110
--
1.5 / 0.30
--
1.00
--
1.000
--
0.0
--
1.000
--
15.0 / 3.00
--
1.00
--
25.0 / 5.00
--
1.00
--
50.0 / 10.00
--
1.00
--
0.00
--
0.00
--
0.000
--
0.00
--
0.00
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--(0.00)
--
10.0 / 2.00
--
25.0 / 5.00
--
100.0 / 20.00
--
200.0 / 40.00
--
--
--
--
⎯ 206 ⎯
6 F 2 S 0 8 2 8
Model2
120
400
410
420
--
--
1.5 / 0.30
--
--
--
1.00
--
--
--
1.000
--
--
--
0.0
--
--
--
1.000
--
--
--
15.0 / 3.00
--
--
--
1.00
--
--
--
25.0 / 5.00
--
--
--
1.00
--
--
--
50.0 / 10.00
--
--
--
1.00
--
--
--
0.00
--
--
--
0.00
--
--
--
0.000
--
--
--
0.00
--
--
--
0.00
--
0.05 / 0.010
--
0.05 / 0.010
1.00
--
1.00
1.000
--
1.000
0.0
--
0.0
1.000
--
1.000
1.00
--
1.00
0.05 / 0.010
--
0.05 / 0.010
1.00
--
1.00
0.05 / 0.010
--
0.05 / 0.010
1.00
--
1.00
0.05 / 0.010
--
0.05 / 0.010
1.00
--
1.00
0.00
--
0.00
0.00
--
0.00
0.00
--
0.00
0.00
--
0.00
0.00
--(0.00)
0.00
1.0 / 0.20
1.00
2.0 / 0.40
1.00
5.0 / 1.00
0.0 / 0.00
10.0
80
0.20
1.00
2.5 / 0.50
0.50
0.40
10.0 / 2.00
25.0 / 5.00
100.0 / 20.00
200.0 / 40.00
20.0 / 4.00
--
--
10.0 / 2.00
--
--
--
25.0 / 5.00
--
--
--
100.0 / 20.00
--
--
--
200.0 / 40.00
--
0.10 / 0.020
--
0.10 / 0.020
0.10 / 0.020
--
0.10 / 0.020
0.10 / 0.020
--
0.10 / 0.020
0.10 / 0.020
--
0.10 / 0.020
0.40
100
100
2.5 / 0.50
0.00
15
0.5 / 0.10
User
Setting