<RTC>
To set the Re-trip control, do the following.
• Enter 0(=Off) or 1(=Direct) or 2(=OC controlled) and press the ENTER key.
<TTSW∗>
• Enter 1(=Trip) to assign a transfer trip command to the binary output for tripping and enter
2(=BO) to assign a transfer trip command to a configurable binary output, and press the
ENTER key. If disabling the transfer trip function, enter 0(=Off) and press the ENTER
key.
Setting the CLP / ICD
The settings for the CLP/ICD are as follows:
• Select "Misc." on the "Scheme sw" screen to display the "Misc." screen.
/ 7
C L E N
O f f / O n
C L D O E N
O f f / O n
D I F - I C D
N A / B L K
O C - I C D
N A / B L K
<CLEN>
To set the Cold load function enable, do the following.
• Enter 1(=On) to enable the Cold Load function and press the ENTER key. If disabling the
Cold Load, enter 0(=Off) and press the ENTER key.
<CLDOEN>
• Enter 1(=On) to enable the Cold Load drop-off and press the ENTER key. If disabling the
Cold Load drop-off, enter 0(=Off) and press the ENTER key.
<DIF-ICD>
• Enter 1(=BLK) to block the DIF tripping when the ICD detects inrush current. If not to block,
enter 0(=NA) and press the ENTER key.
<OC-ICD>
• Enter 1(=BLK) to block the OC, EF and SEF tripping when the ICD detects inrush current. If
not to block, enter 0(=NA) and press the ENTER key.
• After setting, press the END key to display the following confirmation screen.
C h a n g e
E N T E R = Y
• Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.
C L P / I C D
0
0
0
0
s e t t i n g s ?
C A N C E L = N
107
_
6 F 2 S 0 8 2 8