2.4.2
Setting
The table shows the setting elements necessary for the earth fault protection and their setting
ranges.
Element
Range
EF1
0.1 – 25.0 A
(0.02 – 5.00 A)
TEF1
0.00 – 300.00 s
TEF1M
0.010 – 1.500
(TMS)
TEF1R
0.0 – 300.0 s
"ON"
&
1
&
Figure 2.4.1.2 EF2 Earth Fault Protection
"ON"
&
1
&
Figure 2.4.1.3 EF3 Earth Fault Protection
"ON"
&
1
&
Figure 2.4.1.4 EF4 Earth Fault Protection
Step
0.1 A
(0.01 A)
0.01 s
0.001
0.1 s
⎯ 29 ⎯
TEF2
0
t
&
0.00 - 300.00s
&
TEF3
t
0
&
0.00 - 300.00s
&
TEF4
0
t
&
0.00 - 300.00s
&
Default
Remarks
1.5 A
EF1 threshold setting
(0.30 A)
1.00 s
EF1 definite time setting. Required if [MEF1]
= DT.
1.000
EF1 time multiplier setting. Required if
[MEF1] = IEC, IEEE, US or CON.
0.0 s
EF1 definite time delayed reset. Required if
[EF1R] = DEF.
6 F 2 S 0 8 2 8
293
EF2_TRIP
≥1
294
EF3_TRIP
≥1
295
EF4_ALARM
≥1