Toshiba GRL150-100 Series Instruction Manual page 236

Line differential relay
Table of Contents

Advertisement

ENVIRONMENTAL PERFORMANCE CLAIMS
Test
Atmospheric Environment
Temperature
IEC60068-2-1/2
Humidity
IEC60068-2-78
Enclosure Protection
IEC60529
Mechanical Environment
Vibration
IEC60255-21-1
Shock and Bump
IEC60255-21-2
Seismic
IEC60255-21-3
Electrical Environment
Dielectric Withstand
IEC60255-5
High Voltage Impulse
IEC60255-5
Electromagnetic Environment
High Frequency
IEC60255-22-1 Class 3,
Disturbance / Damped
IEC61000-4-12 /
Oscillatory Wave
EN61000-4-12
Electrostatic Discharge
IEC60255-22-2 Class 3,
IEC61000-4-2 / EN61000-4-2
Radiated RF
IEC60255-22-3 Class 3,
Electromagnetic
IEC61000-4-3 / EN61000-4-3
Disturbance
Fast Transient
IEC60255-22-4,
Disturbance
IEC61000-4-4 / EN61000-4-4
Surge Immunity
IEC60255-22-5,
IEC61000-4-5 / EN61000-4-5
Conducted RF
IEC60255-22-6 Class 3,
Electromagnetic
IEC61000-4-6 / EN61000-4-6
Disturbance
Power Frequency
IEC60255-22-7,
Disturbance
IEC61000-4-16 /
EN61000-4-16
Conducted and
IEC60255-25,
Radiated Emissions
EN55022 Class A,
IEC61000-6-4 / EN61000-6-4
Standards
Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
56 days at 40°C and 93% relative humidity.
IP51 (Rear: IP20)
Response - Class 1
Endurance - Class 1
Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Class 1
2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
Three positive and three negative impulses of 5kV(peak),
1.2/50μs, 0.5J between all terminals and between all terminals
and earth.
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
6kV contact discharge, 8kV air discharge.
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
900 and 1890MHz.
4kV, 2.5kHz, 5/50ns applied to all inputs.
1.2/50μs surge in common/differential modes:
HV ports: 2kV/1kV
PSU and I/O ports: 2kV/1kV
RS485 port: 1kV/ -
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
300V 50Hz for 10s applied to ports in common mode.
150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 30m):
30 to 230MHz: <30dB
230 to 1000MHz: <37dB