Toshiba GRL150-100 Series Instruction Manual page 206

Line differential relay
Table of Contents

Advertisement

4. Default setting
Setting 1
Range
No.
Name
5A rating
1
Active gp.
1 - 4
2
Common
CTSVEN
Off / ALM&BLK / ALM
3
IDSVEN
Off / ALM&BLK / ALM
4 Parame
Line name
Specified by user
5
ters
CT
1 - 20000
6
EFCT
1 - 20000
7
Telecom.
SP.SYN.
Master / Slave
8
COM.I/F
PW / OPT
9
RL-MODE
Auto / Manual
10
M.RL
1.0 - 100.0
11 Appl.
MOC1
D / IEC / IEEE / US / C
12
MEF1
D / IEC / IEEE / US / C
13
MSE1
D / IEC / IEEE / US / C
14
OTD
Off / On
15
DIF
DIFEN
Off / On
16
DIF-FS
Off / OC / OCD / Both
17
OC
OC1EN
Off / On
18
MOC1C-IEC
NI / VI / EI / LTI
19
MOC1C-IEEE
MI / VI / EI
20
MOC1C-US
CO2 / CO8
21
OC1R
DEF / DEP
22
OC2EN
Off / On
23
OC3EN
Off / On
24
OC4EN
Off / On
25
EF
EF1EN
Off / On
26
MEF1C-IEC
NI / VI / EI / LTI
27
MEF1C-IEEE
MI / VI / EI
28
MEF1C-US
CO2 / CO8
29
EF1R
DEF / DEP
30
EF2EN
Off / On
31
EF3EN
Off / On
32
EF4EN
Off / On
33
SEF
SE1EN
Off / On
34
MSE1C-IEC
NI / VI / EI / LTI
35
MSE1C-IEEE
MI / VI / EI
36
MSE1C-US
CO2 / CO8
37
SE1R
DEF / DEP
37
SE1S2
Off / On
38
SE2EN
Off / On
39
SE3EN
Off / On
40
SE4EN
Off / On
41
UC
UC1EN
Off / On
42
UC2EN
Off / On
43 Thermal
THMEN
Off / On
44
THMAEN
Off / On
45 BCD
BCDEN
Off / On
46
CBF
BTC
Off / On
47
RTC
Off / DIR / OC
48 Transfer
TTSW1
Off / Trip / BO
49
TTSW2
Off / Trip / BO
50 CLP/ICD
CLEN
Off / On
51
CLDOEN
Off / On
52
DIF-ICD
NA / BLK
53
OC-ICD
NA / BLK
54
DIF
DIFI1
0.50 - 10.00
55
DIFI2
1.0 - 120.0
56
DIFSV
50 - 100
57
TIDSV
0 - 60
58
OC
OC1
0.1 - 25.0
0.00 - 300.00
59
TOC1
60
TOC1M
0.010 - 1.500
61
TOC1R
0.0 - 300.0
62
TOC1RM
0.010 - 1.500
63
OC2
0.1 - 25.0
0.00 - 300.00
64
TOC2
65
OC3
0.1 - 250.0
0.02 - 50.00
0.00 - 300.00
66
TOC3
67
OC4
0.1 - 250.0
0.02 - 50.00
68
TOC4
0.00 - 300.00
69
OC5
0.1 - 250.0
0.02 - 50.00
70
OCD
0.4 (Fixed)
0.08 (Fixed)
71
OC1-k
0.00 - 300.00
72
OC1-α
0.00 - 5.00
73
OC1-C
0.000 - 5.000
74
OC1-kr
0.00 - 300.00
75
OC1-β
0.00 - 5.00
Contents
Units
1A rating
--
Active group
--
AC input imbalance Super Visor Enable
--
Id monitoring control
--
Line name
--
CT ratio
--
SEF CT ratio
--
SP synchronization setting
--
Communication inter-face mode
--
Adjusting mode of the receiving level
% The receiving level value in manually adjusting mode
--
OC1 Delay Type (if OC1EN=On)
--
EF1 Delay Type (if EF1EN=On)
--
SEF1 Delay Type (if SE1EN=On)
--
The function of open terminal detection use or not
--
DIF Enable
--
DIF Fail Safe Enable
--
OC1 Enable
--
OC1 IEC Inverse Curve Type (if MOC1=IEC)
--
OC1 IEEE Inverse Curve Type (if MOC1=IEEE)
--
OC1 US Inverse Curve Type (if MOC1=US)
--
OC1 Reset Characteristic (if MOCI=IEEE,orUS)
--
OC2 Enable
--
OC3 Enable
--
OC4 Enable
--
EF1 Enable
--
EF1 IEC Inverse Curve Type (if MEF1=IEC)
--
EF1 IEEE Inverse Curve Type (if MEF1=IEEE)
--
EF1 US Inverse Curve Type (if MEF1=US)
--
EF1 Reset Characteristic (if MEFI=IEEE,orUS)
--
EF2 Enable
--
EF3 Enable
--
EF4 Enable
--
SEF1 Enable
--
SEF1 IEC Inverse Curve Type (if MSE1=IEC)
--
SEF1 IEEE Inverse Curve Type (if MSE1=IEEE)
--
SEF1 US Inverse Curve Type (if MSE1=US)
--
SEF1 Reset Characteristic (if MSEI=IEEE,orUS)
--
SEF1 Stage 2 Timer Enable (if MSE1EN=On)
--
SEF2 Enable
--
SEF3 Enable
--
SEF4 Enable
--
UC1 Enable
--
UC2 Enable
--
Thermal OL Enable
--
Thermal Alarm Enable
--
Broken Conductor Enable
--
Back-trip control
--
Re-trip control
--
Transfer trip Enable(CH1)
--
Transfer trip Enable(CH2)
--
Cold Load Protection Enable
--
Cold Load drop-off Enable
--
DIF trip blocked or not by inrush current detection
--
OC/EF/SEF trip blocked or not by inrush current detection
0.10 - 2.00
A
DIF1 Threshold setting (if DIFEN=On)
0.2 - 24.0
A
DIF2 Threshold setting (if DIFEN=On)
% Minimum operating current of DIFSV
s
Id err detected timer
0.02 - 5.00
A
OC1 Threshold setting (if OC1EN=On)
s
OC1 Definite time setting (if MOC1=DT)
--
OC1 Time multiplier setting (if MOC1=IEC,IEEE,US)
s
OC1 Definite time reset delay (if OC1R =DEF)
--
OC1 Dependent time reset time multiplier (if OC1R=DEP)
0.02 - 5.00
A
OC2 Threshold setting (if OC2EN=On)
s
OC2 Definite time setting (if MOC2=DT)
A
OC3 Threshold setting (if OC3EN=On)
s
OC3 Definite time setting (if OC3EN=On)
A
OC4 Threshold setting (if OC4EN=On)
s
OC4 Definite time setting (if OC4EN=On)
A
OC5 Threshold setting
A
OCD Threshold setting
--
Configurable IDMT Curve setting of OC1.
--
ditto
--
ditto
--
ditto
--
ditto
Default Setting of Relay Series(5A rating / 1A rating)
Model1
100
110
--
--
D
--
--
On
--
NI
--
MI
--
CO2
--
DEF
--
Off
--
Off
--
Off
--
--
--
--
--
--
--
--
--
⎯ 205 ⎯
6 F 2 S 0 8 2 8
Model2
120
400
410
420
1
ALM
ALM
no-name
400
400
Master
OPT
Auto
20.0
DT
--
--
D
--
D
--
D
Off
On
Off
On
NI
MI
CO2
DEF
Off
Off
Off
--
--
On
--
--
--
NI
--
--
--
MI
--
--
--
CO2
--
--
--
DEF
--
--
--
Off
--
--
--
Off
--
--
--
Off
--
On
--
On
NI
--
NI
MI
--
MI
CO2
--
CO2
DEF
--
DEF
Off
--
Off
Off
--
Off
Off
--
Off
Off
--
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
NA
NA
5.00 / 1.00
15.0 / 3.0
50
10
5.0 / 1.00
1.00
1.000
0.0
1.000
25.0 / 5.00
1.00
50.0 / 10.00
1.00
100.0 / 20.00
1.00
2.5 / 0.50
--
0.00
0.00
0.000
0.00
0.00
User
Setting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl150-400 seriesGrl150-100a-10-10