Toshiba GRL150-100 Series Instruction Manual page 26

Line differential relay
Table of Contents

Advertisement

92
OC4-A
93
OC4-B
94
OC4-C
OC4-EN
+
"ON"
373
ICD
OC_IC_BLK
1683
By PLC
[OC-ICD]
(+)
"
"
BLK
OC4_BLOCK
1559
1
OC4_INST_TP
1623
2.3.3
Setting
The table shows the setting elements necessary for the phase overcurrent protection and their
setting ranges.
Element
Range
OC1
0.1 – 25.0 A
(0.02 – 5.00 A)(*)
TOC1
0.00 – 300.00 s
TOC1M
0.010 – 1.500
(TMS)
TOC1R
0.0 – 300.0 s
TOC1RM
0.010 – 1.500
(RTMS)
OC2
0.1 – 25.0 A
(0.02 – 5.00 A)(*)
TOC2
0.00 – 300.00 s
OC3
0.1 – 250.0 A
(0.02 – 50.00 A)(*)
TOC3
0.00 – 300.0 s
OC4
0.1 – 250.0 A
(0.02 – 50.00 A)(*)
TOC4
0.0 – 300.0 s
[OC1EN]
Off / On
[MOC1]
DT/IEC/IEEE/US/CON
[MOC1C]
MOC1C-IEC
NI / VI / EI / LTI
MOC1C-IEEE
MI / VI / EI
MOC1C-US
CO2 / CO8
[OC1R]
DEF / DEP
[OC2EN]
Off / On
&
&
&
&
1
&
Figure 2.3.2.4 OC4 Phase Overcurrent Protection
Step
0.1 A
(0.01 A)
0.01 s
0.001
0.1 s
0.001
0.1 A
(0.01 A)
0.01 s
0.1 A
(0.01 A)
0.01 s
0.1 A
(0.01 A)
0.01 s
⎯ 25 ⎯
TOC4
t
0
≥1
0
t
≥1
t
0
≥1
0.00 - 300.00s
&
&
&
Default
Remarks
5.0 A
OC1 threshold setting
(1.00 A)
1.00 s
OC1 definite time setting. Required if [MOC1] = DT.
1.000
OC1 time multiplier setting. Required if [MOC1] =
IEC, IEEE, US or CON.
0.0 s
OC1 definite time delayed reset. Required if [OC1R]
= DEF.
1.000
OC1 dependent time delayed reset time multiplier.
Required if [OC1R] = DEP.
5.0 A
OC2 threshold setting
(1.00 A)
1.00 s
OC2 definite time setting.
50.0 A
OC3 threshold setting
(10.00 A)
1.00 s
OC3 definite time setting
100.0 A
OC4 threshold setting
(20.00 A)
1.00 s
OC4 definite time setting
On
OC1 Enable
DT
OC1 time characteristic
OC1 inverse curve type.
NI
Required if [MOC1] = IEC.
MI
Required if [MOC1] = IEEE.
CO2
Required if [MOC1] = US.
DEF
OC1 reset characteristic. Required if [MOC1] =
IEEE, US or CON.
Off
OC2 Enable
6 F 2 S 0 8 2 8
285
284
≥1
OC4_ALARM
286
287

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl150-400 seriesGrl150-100a-10-10