Toshiba GRL150-100 Series Instruction Manual page 31

Line differential relay
Table of Contents

Advertisement

Element
Range
TEF1RM
0.010 – 1.500
(RTMS)
EF2
0.1 – 25.0 A
(0.02 – 5.00 A)
TEF2
0.00 – 300.00 s
EF3
0.1 – 250.0 A
(0.02 – 50.00 A)(*)
TEF3
0.00 – 300.00 s
EF4
0.1 – 250.0 A
(0.02 – 50.00 A)(*)
TEF4
0.00 – 300.00 s
[EF1EN]
Off / On
[MEF1]
DT/IEC/IEEE/US/CON
[MEF1C]
MEF1C-IEC
NI / VI / EI / LTI
MEF1C-IEEE
MI / VI / EI
MEF1C-US
CO2 / CO8
[EF1R]
DEF / DEP
[EF2EN]
Off / On
[EF3EN]
Off / On
[EF4EN]
Off / On
[OC-ICD]
NA / BLK
(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current values are in
the case of a 5 A rating.
Step
Default
Remarks
0.001
1.000
EF1 dependent time delayed reset time
multiplier. Required if [EF1R] = DEP.
0.1 A
1.5 A
EF2 threshold setting
(0.01 A)
(0.30 A)
0.01 s
1.00 s
EF2 definite time setting.
0.1 A
25.0 A
EF3 threshold setting
(0.01 A)
(5.00 A)
0.01 s
1.00 s
EF3 definite time setting
0.1 A
50.0 A
EF4 threshold setting
(0.01 A)
(10.00 A)
0.01 s
1.00 s
EF4 definite time setting
On
EF1 Enable
DT
EF1 time characteristic
EF1 inverse curve type.
NI
Required if [MEF1] = IEC.
MI
Required if [MEF1] = IEEE.
CO2
Required if [MEF1] = US.
DEF
EF1 reset characteristic. Required if [MEF1]
= IEEE, US or CON.
Off
EF2 Enable
Off
EF3 Enable
Off
EF4 Enable
NA
OC/EF/SEF blocked by inrush current
⎯ 30 ⎯
6 F 2 S 0 8 2 8