4.5 CAN interface

The CAN-bus is connected via terminal plug 1. A maximum of 32 CAN users
can be connected in one bus segment.
The CAN-bus needs a terminating resistance of 120 Ω in the first and last bus
users. A terminating impedance is integrated into the MP60 module which is
activated by the S14 DIP switches (see page 14).
Fig. 4.7: Connect CANinterface
CAN
connection
in accordance
with Fig. 4.7
First device in
the bus line
Switch on terminating resistance
in the PME (see page 14)
Fig. 4.8: CAN-bus operation with several modules (as per Standard maximum 32)
NOTE
If the first or last device in a bus circuit is not a PME module, then a
120 W resistance must be switched on at these pieces of equipment.
A0616-13.4 en