The supply connection, as well as the signal and sense leads, must be installed in such a way that electromagnetic interference does not adversely affect device functionality (HBM recommendation: ”Greenline shielding design”, downloadable from the Internet at http://www.hbm.com/Greenline). Automation equipment and devices must be covered over in such a way that adequate protection or locking against unintentional actuation is provided (such as access checks, password protection, etc.).
Page 5
PME-MP60/MP07 Use in accordance with the regulations The MP60 and MP07 module and their connected transducers may be used for measurement tasks only and directly related control tasks. To ensure safe operation, the transducer may only be used as specified in the operating manual.
Page 6
PME-MP60/MP07 Residual dangers The scope of performance and supply of the MP60 or MP07 covers only part of the measurement technology. In addition, equipment planners, installers and operators should plan, implement and respond to the safety engineering considerations of measurement technology in such a way as to minimize re- sidual dangers.
Page 7
Greenline shielding only (conncect the shield of the transducer cable to the plug housing). The cables of the digital inputs and outputs of the MP60/MP60DP should not be longer than 30 m or should they be routed outside the building where the system is located.
Page 8
Conversions and modifications HBM’s express consent is required for modifications affecting the transdu- cers’s design and safety. HBM does not take responsibility for damage resul- ting from unauthorized modifications. The product is delivered from the factory with a fixed hardware and software configuration.
HBM T10F-SF1 and T10F-SU2 torque flanges. The MP60 module is set up and parameters assigned via the keyboard and display or with the aid of the PME Assistent. The PME Assistent gives you a simple operator interface under MS-Windows for assigning parameters to the modules (described in the ”PME Assistent”...
Page 10
The following HBM torque transducers may derive their excitation from an MP07 module: T10F-KF1, T30FNA, T32FNA, T34FN, T36FN The MP07 module, like the MP60, is connected to a 24 V supply voltage and delivers the following output voltages (short-circuit proof): +15 VDC, 100 mA...
PME-MP60/MP07 Selecting amplifier settings with DIP switches NOTE The adjustment/alteration of DIP switch settings must take place before mounting the PME. Various settings are defined with the aid of DIP switches. These are the settings for terminating resistance, frequency input signals, input connection...
PME-MP60/MP07 Mounting/dismounting the MP60/MP07 Fig. 3.1: Mounting on a support rail Fig. 3.2: Dismounting A0616-13.4 en...
Page 16
PME-MP60/MP07 Fig. 3.3: Fitting of a second spring fore more stable mounting of the module on the DIN rail CAUTION The support rail must be on protection circuit potential A0616-13.4 en...
Fig. 3.4: Connecting the flat ribbon cable Several MP60 or MP07 modules may be connected over one flat ribbon cable. This cable is used for local connection of the supply voltage and synchronization between the modules. You should not interconnect more than 8 modules with one flat ribbon cable.
Connections WARNING Please take note of the safety instructions before putting the device into operation. 4.1 Functional overview of MP60/MP07 Local linking of CAN-bus, supply voltage and synchronization between the modules Terminal plug 1: MP60 Voltage supply and CAN-bus, Synchronization...
4.2 Supply voltage and control inputs/outputs MP60 Four removable terminal plugs are provided for connection. Connect voltage supply Warning The MP60 module must be connected to an external voltage supply of 18-30 V (24 V nom. D Twist wires of the voltage supply and fit end sleeves for strands.
PME-MP60/MP07 4.2.1 External supply voltage for control outputs (MP60) Example: PLC connection MP60 module Relay max. 100 mA OUT3 max. 100 mA OUT1 24 V* 0 V* 0 V* Terminal plug 4 Fig. 4.2: Connection to a PLC Control inputs are provided at terminal plug 3 and control outputs at terminal plug 4, and are electrically isolated internally from the supply voltage (see also Chapter 6, ”Declaring the significant parameters”...
Fig. 4.3: Pin assignment for terminal plug 1 See Chapter 4.4 NOTE Use standard HBM cable for the transducer connection. When using other shielded, low-capacitance measuring cable, connect the trans- ducer cable shielding to the connector housing in accordance with the HBM Greenline concept (Internetdownload http://www.hbm.com/Green-...
Measurement signal for rotation speed, 0° , F1 (+) Measurement signal for rotation speed, 0° , F1 (-) Measurement signal for rotation speed, 90° , F2 (-) Hsng. Cable shielding Measurement signal for rotation speed, 90° , F2 (+) Transducer error Fig. 4.4: Connection for MP60 A0616-13.4 en...
Page 23
(5 - 30 V) peak-to-peak (90° out-of-phase for detection Transducer of direction of rotation) shaft Hsng. Cable shielding Measurement signal for rotation speed, F1 (+), 25 V (5 - 30 V) peak-to-peak Transducer error Fig. 4.5: Connection for MP60 and MP07 A0616-13.4 en...
Page 24
Fig. 4.6: Connection for MP60 NOTE The MP60(DP) can indicate the transducer errors generated by the tor- que sensor. But to do this, the error signal from the torque sensor must be connected across Pin 7 of the transducer plugs (15−pin sub−D plugs) on the MP60(DP).
The CAN-bus needs a terminating resistance of 120 Ω in the first and last bus users. A terminating impedance is integrated into the MP60 module which is activated by the S14 DIP switches (see page 14).
PME-MP60/MP07 4.6 Synchronization (MP60) Synchronization of modules guarantees the simultaneous acquisition and processing of measurement data. Slave Master 1 2 3 4 5 6 1 2 34 5 6 Fig. 4.9: Set up master/slave When synchronising several modules, one device is to be declared as the master.
PME-MP60/MP07 Setting up and operation (MP60) 5.1 Operating principles Display in measuring mode: Measured value -18.00 Status field Unit ↓ ↑ Flashes in status field, if parameter value is editable These keys are pressure-sensitive: Hold key down - values run through (the harder you press, the faster they run...
Page 28
PME-MP60/MP07 Measuring mode Password status active Password status inactive (factory setting): 2 secs. 2 secs. DIALOG PASSWORD Set-up mode Enter password: Password ↓ ↑ Input mode Enter required password (factory setting 0) Confirm Example: Enter numerical Select table value value...
Page 29
PME-MP60/MP07 During measurement you can press - view on display: 1. measured value 2. analogue output value 3. status of digital I/Os 4. the error list The symbol is displayed in the status field , this indicates an error which is described in the error list.
If the error message HardwOvf is displayed at this point, please refer to the Chapter called 8 ”Error messages” for further details. In addition, the yellow LED indicates that the MP60 is ready to start measuring. You will find the meanings of other LED signals in the chapter called 8 ”Error messages”.
5.3 Guide to all groups and parameters Groups PARAM. TRANSD.- ANALOG LIMIT VAL. PEAKVAL. PROFI- ADDITION DIALOGUE DISPLAY TRANSDUCER CONDITIoNING IN/OUT CAN-BUS CALIBRAT OUTPUT 1..4 STORE FUNCTION Password Load ? DecPoint Unit P1Meas.? >0< Set ? SourceVo Enable Enable Output1 Baudrate Address AmplType...
5.3.1 Set up all parameters 2sec A0616-13.4 en HBM Meas. value PassStat active Groups Transducer DISPLAY PARAM. SET PASSWORD DIALOGUE .00000 ↓ ↑ ↓ ↑ ParaS.1 ↓ ↑ _ _ _ _ Password _ _ _ _ Password ↓ ↑...
Page 33
Zero kNm 0.000 ↓ ↑ Bessel FiltChar Butterw l/mi ↓ ↑ NVal kHz 0.00000 Back to ↓ ↑ MAINGRP NVal kNm 0.00000 Back to ↓ ↑ Trans Err MAINGRP Back to depending on the unit selected A0616-13.4 en HBM MAINGRP...
Page 34
Groups A0616-13.4 en HBM Analog output PEAKVAL. CAN-BUS IN / OUT LIMIT VAL.1 LIMIT VAL.2...4 STORE LimVal1 ↓ ↑ LimVal2 LimVal3 Enable LimVal4 ↓ ↑ Output1 ↓ ↑ Enable Motion Error Accordingly Pulse Gross Output2..4 ↓ ↑ Source inactiv InputMin ↓...
Page 35
↓ ↑ Slow Gross ↓ ↑ Keyboard Fast Output Medium PkValMax PkValMin PkVal PP HW-Vers Back to MAINGRP ↓ ↑ OutR. ms ↓ ↑ float PDO-Frmt int32 ↓ ↑ AutoOPER Back to MAINGRP depending on the unit selected A0616-13.4 en HBM...
PME-MP60/MP07 5.4 Example: measuring Md and N with torque transducer T10F (24 V supply) Both the T10F and the MP60 are set to symmetrical signals at the factory. Torque measurement Measurement preparation: Use the standard cable md-cab149. " Connect the 24 V external supply voltage to terminal plug 4 as well (see "...
Page 37
PME-MP60/MP07 The T10F is set by using sensitivity. To achieve greater accuracy, you must use the integrated shunt to calibrate the T10F. Calibration with integrated shunt: The transducer must be load−free! Group: TRANSD.-CALIBRAT P1Meas.? YES (corresponds to zero point measurement)
Page 38
PME-MP60/MP07 Enter T10F characteristic values: Group: TRANSDUCER Unit: U/min Input range: 1 MHz Zero index (+) Frq x 4 Direction of rotation (only possible if F1 and F2 are active) Switching threshold 2.5 V Glitch filter Zero kHz Zero U/min...
PME-MP60/MP07 Declaring the significant parameters Group Parameters Meaning DIA− Password Specifying (changing) a password, 0000 - 9999 LOGUE (Factory preset password: 0000) PassStat Define password status: active=password must be entered; inactive=PME can be operated without a password I.ParaS to Access to group via keyboard free or locked.
Page 40
The direction of rotation information is analysed when F2 is activated . A negative direction of rotation as defined by HBM is shown by a - (minus) sign. Threshol Switching threshold from which the input signal is detected Suppresses interference spikes with a duration of t3.2 μs...
Page 41
PME-MP60/MP07 Group Parameters Meaning CONDITIO >0< kNm Enter zero value. Zeroing effects both, the gross value and NING the net value. >0< Set ? Trigger zero balance; current measurement value (physical unit) zero >0< save Each time there is a zeroing procedure the zero value is adopted into the EEPROM (service life 100.000 cycles)
Page 42
PME-MP60/MP07 Group Parameters Meaning ANALOG SourceVo You can choose the gross or net values, as well as the peak OUTPUT value as the source of the analogue signal. Mode Vo Use DIP switches S11 to specify the signal mode for the analogue output.
Page 43
PME-MP60/MP07 Group Parameters Meaning LIMIT VAL. Source You can select one of the following as the source of the limit 1...4 value signal: Gross, Net, Peak value Max/Min/Peak-to-peak SwtchDir Functions and parameters of limit values Value LVS1, ON Value Hyst...
Page 44
PME-MP60/MP07 Inputs /Outputs Terminal plug 3: provided here for the control of PME functions are 4 inputs. Terminal plug 4: Here you have 4 outputs available. Group Parameters Meaning IN/OUT Output Outputs 1 - 4 can be assigned the following functions for each...
Page 45
PME-MP60/MP07 Group Parameters Meaning IN/OUT PkMomMax ”Peak value” operating mode PkMomMin Measurement signal PkHldMax PkHldMin Trend of stored value Hold Hold Function Operating Peak value (Store1) Current value mode ”Current value” operating mode Measurement signal Hold Function Operating Current value...
Page 46
PME-MP60/MP07 Group Parameters Meaning ADDITION >0<Rf Referenznull FUNCTION Ein Wegaufnehmer 〈"20 mm Nennmeßweg) ist vom Fun- dament aus gemessen in einer Höhe von 1 m befestigt. Bei einem Nullsetzen wird der Analogausgang auf 0 V abgegli- chen. Der Anzeigewert wird auf >0<Ref (+1000 mm) abgeg- lichen.
CAN interface description (MP60 only) 7.1 General The MP60 module has a built-in CAN interface, via which both measured values (data) can be transferred and parameters can be assigned to the module. You are free to select the baud rate, but the maximum is 1 MBaud.
Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Writing a parameter: Send value (PC or PLC on MP60/MP07) Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á...
Page 49
Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Response in the event of an error when reading or writing parameters: Error acknowledge (MP60/MP07 on PC or PLC) Á Á Á Á Á Á Á Á Á...
PME-MP60/MP07 7.4 Object directory (communications profile section) Communications profile section according to CAN-open (CIA-DS301) Index Sub- Name Data type Attr. Values Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á...
Page 51
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á 1801 0..2 2.
Page 52
PME-MP60/MP07 SDO parameter: Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index Subindex...
PME-MP60/MP07 7.6 Object directory: manufacturer-specific objects Parameters relating to measured values are coded with figures scaled in the appropriate range as Long (32 bit integer). The position of the decimal point is defined in the object 2120Hex. Alternatively, these quantities are also available as floating decimal point values (IEEE754-1985 32 Bit format) (see page 64).
Page 55
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á...
Page 56
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 57
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 58
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 59
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index Sub-...
Page 60
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 61
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 62
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
Page 63
PME-MP60/MP07 Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Index...
PME-MP60/MP07 7.8 Examples Example 1: Reading the net measured value as a floating value using SDO transfer from the amplifier with Module address 3. Protocol at the amplifier: Á Á Á Á Á Identifier Á Á Á Á Á Á Á Á Á...
PME-MP60/MP07 Error messages/operating status (LED) Depending on the display mode, various error messages may be displayed in place of the measured value: Signal status (mode) possible error message Grs+Ovf CntrOvfl Scal.Err - - - - - - - Grs-Ovf Init Err...
Page 68
40 NOTE The MP60(DP) can indicate the transducer errors generated by the tor- que sensor. But to do this, the error signal from the torque sensor must be connected across Pin 7 of the transducer plugs (15−pin sub−D plugs) on the MP60(DP).
Page 69
PME-MP60/MP07 Operating status: Status Meaning colour Measuring mode Bus mode Green Steady Ready to take measurements CAN Operational (PDO transfer light possible) Green Flashing Data is transferred via the interface Yellow Steady Ready to take measurements CAN-bus Pre-operational (no PDO...