Measures And Requirements For Shielded Voltage Supply Of The Module - Bosch Rexroth IndraControl S67 Manual

8 inputs/outputs – 0.5 a (8xm12)
Hide thumbs Also See for Rexroth IndraControl S67:
Table of Contents

Advertisement

DOK-CONTRL-S67DIO8M12*-AP03-EN-P
Rexroth IndraControl S67 Digital Module 8 Inputs/Outputs – 0.5 A (8×M12)
13.4
Measures and Requirements for Shielded Voltage Supply of
the Module
Using Interference-Free Module in Safety Applications
NOTICE
The supply voltages U
and U
A
fuse to ensure that the current flow is interrupted if an error occurs. U
U
can be protected with a fuse cut-out each acc. to EN 60127-2 or with an
LS
electronic fuse each. Fuse cut-outs have to comply with the following techni‐
cal specifications acc. to EN 60127-2:
G-fuse cartridge
Rated current 4 A
Slow-blow
Current pulse insensitive
Large or increased circuit-breaking capacity
Rated voltage ≥ 60 V DC
Time-current characteristics: 275 % of the nominal current, correspond‐
ing to 11 A, maximum 80 s
NOTICE
To rule a short circuit of the voltage supply U
is required, that the wires U
according to EN 60204-1 or EN ISO 13849-2. The shield requires a coverage
of 85 % and has to be defined and reliably connected to the connector.
NOTICE
Connect the ground shield of the connecting lead to the functional ground
connection FE of the non-reactive modules to the 0 V U
Moreover, an insulation monitoring can be used according to EN 61557.
Please see the following figures:
Fuse
U LS
24 V
U A
FE
Fig. 13-1:
Connecting diagram for mutual voltage supply
Bosch Rexroth AG
Protect the supply voltages with an external
fuse!
have to be protected by a suitable external
LS
Shielded version of U
necting lead required in case of an unprotec‐
ted laying!
with an external voltage out, it
A
and 0 V U
in the connecting lead are shielded
A
A
Apply ground shield or use insulation moni‐
toring!
Safety relay
77/93
and
A
and 0 V U
in con‐
A
A
and 0 V U
leads.
LS
A
U LS
Module
IndraControl S67
U A
FE