Commissioning; General Information - Bosch Rexroth IndraControl S67 Manual

8 inputs/outputs – 0.5 a (8xm12)
Hide thumbs Also See for Rexroth IndraControl S67:
Table of Contents

Advertisement

DOK-CONTRL-S67DIO8M12*-AP03-EN-P
Rexroth IndraControl S67 Digital Module 8 Inputs/Outputs – 0.5 A (8×M12)
7

Commissioning

7.1

General Information

NOTICE
If connections have not been closed with protective caps, liquid or dirt can
penetrate the S67-DIO8-M12×8 module and destroy it. Protect all non-re‐
quired connection with protective caps to comply with protection class IP 67.
Before commissioning the IndraControl S67 station, check the following
points:
A field bus coupler of the IndraControl S67 series
M12×8 module have been mounted correctly
All required supply, sensor or actuator and S-BUS lines as well as the
S-BUS terminator are screwed tightly at the provided connections (refer
to
chapter 6 "Connecting Data and Supply Cables" on page
An appropriate potential equalization was executed at the system
Shielding was carried out correctly
1)
Refer to the field bus coupler application manuals (IndraControl S67)