DOK-CONTRL-S67DIO8M12*-AP03-EN-P
Rexroth IndraControl S67 Digital Module 8 Inputs/Outputs – 0.5 A (8×M12)
7
Commissioning
7.1
General Information
NOTICE
If connections have not been closed with protective caps, liquid or dirt can
penetrate the S67-DIO8-M12×8 module and destroy it. Protect all non-re‐
quired connection with protective caps to comply with protection class IP 67.
Before commissioning the IndraControl S67 station, check the following
points:
●
A field bus coupler of the IndraControl S67 series
M12×8 module have been mounted correctly
●
All required supply, sensor or actuator and S-BUS lines as well as the
S-BUS terminator are screwed tightly at the provided connections (refer
to
chapter 6 "Connecting Data and Supply Cables" on page
●
An appropriate potential equalization was executed at the system
●
Shielding was carried out correctly
1)
Refer to the field bus coupler application manuals (IndraControl S67)
Bosch Rexroth AG
Exposed connections!
1)
43/93
Commissioning
and the S67-DIO8-
35)