Specification - Smartgen HGM1790N User Manual

Genset controller
Hide thumbs Also See for HGM1790N:
Table of Contents

Advertisement

3.

SPECIFICATION

Item
Working Voltage
Power Consumption
Alternator Voltage Input
Alternator Frequency
Speed Sensor Voltage
Speed Sensor Frequency
Start Relay Output
Fuel Relay Output
Aux. Output1
Aux. Output2
Aux. Output3
Programmable
Digital
Input
Case Dimensions
Panel Cutout
CT Secondary Current
Working conditions
Storage Condition
Protection Level
Insulation Intensity
Weight
HGM1790N Genset Controller User Manual
Table 2 Technical Parameters
DC8. 0V to 35. 0V, Continuous Power Supply
<1.2W (Standby mode: ≤0.5W)
AC 15V ~ AC 360 V (ph-N)
50Hz/60Hz
1.0V to 24V (RMS)
Max. 10, 000Hz
1Amp DC28V DC B+ power supply
1Amp DC28V DC B+ power supply
1Amp DC28V DC B+ power supply
1Amp DC28V DC B+ power supply
1Amp DC28V DC B+ power supply
Active when connected to B-
95mm x 86mm x 46.5mm
78mm x 66mm
Rated: 5A
Temperature: (-25~+70)ºC Humidity: (20~93)%RH
Temperature: (-25~+70)ºC
IP55: When waterproof rubber gasket installed between the
controller and panel fascia.
Attach AC2.2kV voltage between AC high voltage terminal and low
voltage terminal (leak current below 3mA in 1 minute).
0.18kg
Content