Smartgen HGM1790N User Manual page 18

Genset controller
Hide thumbs Also See for HGM1790N:
Table of Contents

Advertisement

No.
Parameter
Low
Oil
P23
Pressure
Low
Liquid
P24
Level
Battery
Over
P25
Volts
Battery
Under
P26
Volts
P27
CT Ratio
P28
Full-load Current (5-1900)A
Over
Current
P29
Percentage
Over
Current
P30
Delay
HGM1790N Genset Controller User Manual
Default
Range
Value
(0-400)kPa
103
(0-100)%
10
(12-40)V
33.0
(4-30)V
8.0
(5-6000)/5
500
500
(50-130)
120
(0-3600)s
60
Description
sensor
which
connected
temperature sensor input port. If the set
value is 140, high temperature signal will
not
be
sent
(this
temperature
sensor,
temperature signal via config. input
port).
When the external pressure sensor value
falls below this threshold, low oil
pressure delay begins. Detection begins
after safely on delay. If the set value is 0,
low oil pressure signal is not sent (this
only concerns pressure sensor and does
not concern low oil pressure warning
signal via configurable input port)
When the liquid level of the external
sensor falls below this value and stays
so for 10s, low liquid level signal is sent
and
warning
without
initiated.
When battery voltage exceeds this value
and stays so for 20s, Battery Over Volts
signal is sent and warning without
shutdown is initiated.
When battery voltage falls below this
value and stays so for 20s, Battery Under
Volts signal is sent and warning without
shutdown is initiated.
Current transformer ratio default as
500:5.
It is the rated current of generator, which
is apply for calculating over current with
load.
Over current delay starts when current
with load is greater than value of
full-load current multiply over current
percentage.
When current with load exceeds preset
value and stays so over delay time, over
to
the
only
concerns
not
high
shutdown
is
Page 18 of 31