HGM1790N Genset Controller User Manual
Type
Controller sent alarms when generator current is
Current
higher than the preset value and lasts for over than
Shut Alarm
delay value (over current action is selected as
"Cooling Shutdown").
Detection after safe running delay, controller sent
alarms when generator voltage is higher than over
Shut Alarm
than voltage threshold and lasts for over than
voltage abnormal delay value.
Detection after safe running delay, controller sent
alarms when generator voltage is lower than under
Shut Alarm
voltage threshold and lasts for over than voltage
abnormal delay value.
Controller Sent alarms when genset fail to start in
Shut Alarm
preset attempts.
Controller sent alarms when auxiliary input port,
Alarm
Shut Alarm
which is configured as "auxiliary shutdown alarm
input", is active.
Controller sent alarms when fuel level is lower than
Warn Alarm
low fuel level threshold and lasts for over 10s.
Controller sent alarms when low fuel level input is
Warn Alarm
active.
Sensor
Controller sent alarms when Fuel level sensor
Circuit
Warn Alarm
resistance value is above 6000Ω or under 5Ω.
Controller sent alarms when genset fail to stop in
Warn Alarm
stop duration.
Controller sent alarms when battery voltage is
Warn Alarm
lower than under voltage threshold and lasts for
over 20s.
Controller sent alarms when battery voltage is
Warn Alarm
higher than over voltage threshold and lasts for
over 20s.
Triggering Condition