9 Troubleshooting and Maintenance
I I t t e e m m
Cable entry
Electrical
Connection

9.2.3 Cleaning Air Inlet and Outlet

A significant amount of heat is generated when the inverter is working.
In order to maintain good ventilation, please check to make sure the air inlet and outlet
are not blocked.
Clean the air inlet and outlet with soft brush or vacuum cleaner if necessary.

9.2.4 Fan Maintenance

Stop the inverter and disconnect it from all power supplies before
maintenance.
Lethal voltage still exists in the inverter. Please wait for at least 5 minutes
and then perform maintenance work.
Only qualified electricians can maintain the fans.
Fans inside the inverter are used to cool the inverter during operation. If the fans do not
operate normally, the inverter may not be cooled down and inverter efficiency may de-
crease. Therefore, it is necessary to clean dirty fans and replace the broken fans in a
timeiy manner.
The operation procedure is as follows:
step 1 Stop the inverter (see 8.1 Disconnecting the Inverter).
step 2 Loosen the screw on the sealing plate of the fan module.
86
M M e e t t h h o o d d
Check whether the cable entry is in-
sufficiently sealed or the gap is ex-
cessively large, and reseal the entry
when necessary.
Check whether all cable are firmly
connected in place.
Check whether a cable is damaged,
especially the part contacting the
metal enclosure.
User Manual
P P e e r r i i o o d d
Once a year
Six months to a year