7 iSolarCloud App
P P a a r r a a m m e e t t e e r r
QP_P3
QP_K1
QP_K2
QP_K3
QP_EnterVoltage
QP_ExitVoltage
QP_EXitPower
QP_EnableMode
Q(U)Curve
QU_V1
QU_Q1
68
D D e e f f i i n n i i t t i i o o n n / / S S e e t t t t i i n n g g
D D e e s s c c r r i i p p t t i i o o n n
Output power at P3 on the Q
(P) mode curve (in
percentage)
Power factor at P1 on the Q
(P) mode curve
Power factor at P2 on the Q
(P) mode curve
Power factor at P3 on the Q
(P) mode curve
Voltage percentage for Q(P)
function activation
Voltage percentage for Q(P)
function deactivation
Power percentage for Q(P)
function deactivation
Unconditional activation/de-
activation of Q(P) function
Select the corresponding
curve according to local
regulations
Pre-set grid voltage U1 that
is reactive according to the
grid voltage
Pre-set proportion of reactive
power according to the grid
voltage U1
User Manual
R R a a n n g g e e
20.0%~100.0%
Curve A/Curve
C:0.800~1.000
Curve B: [-0.600~0.600]
*Active Overload Rate/
1000
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]
*Active Overload Rate/
1000
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]
*Active Overload Rate/
1000
100.0%~110.0%
90.0%~100.0%
1.0%-20.0%
Yes/No
Curve A/Curve B/Curve C*
80.0%~100.0%
[-60.0%-0]* Overload
Rate/1000