The mode DRM0 is supported by the inverter.
table 5-4 Method of Asserting DRMs
M M o o d d e e
DRM0
Enable the DRM function through the iSolarCloud APP. If there are any prob-
lems, contact SUNGROW.
The DRM function is only applicable to devices for Australia and New Zealand.

5.12.2 Connection Procedure

step 1 Remove the communication junction box,
step 2 Strip the insulation layer of the Ethernet cable with a wire stripper, and insert the signal
wires to the RJ45 connector. Crimp the RJ45 connector with a crimping tool.
M M e e t t h h o o d d o o f f A A s s s s e e r r t t i i n n g g
Asserted by shorting pins 5 and 6
Asserted when the impedance between pins 5 and 6 is detected to be
above 20kΩ
see" Remove the Junction
5 Electrical Connection
Box".
49