Connection Procedure(Terminal Block) - Sungrow SG30CX User Manual

Pv grid-connected inverter
Hide thumbs Also See for SG30CX:
Table of Contents

Advertisement

User Manual

5.10.3 Connection Procedure(Terminal Block)

RS485 communication cables should be shielded twisted pair cables or
shielded twisted pair Ethernet cables.
There are three communication terminals, and the silkscreen marks are
COM1/COM2/COM3. Please choose according to the actual situation.
step 1 Remove the communication junction box,
step 2 Strip the protection layer and insulation layer by appropriate length.
step 3 Loosen the swivel nut of the junction box and select an appropriate seal according to
cable outer diameter. Lead the cable through the swivel nut, seal, and junction box
successively.
O O u u t t e e r r D D i i a a m m e e t t e e r r D D ( ( m m m m ) )
4.5 ~ 6
6 ~ 12
12 ~ 18
step 4 Secure the cable to the terminal base.
see" Remove the Junction
S S e e a a l l
c
a + b
b
5 Electrical Connection
Box".
43