3. Use a separate transformer – the 40 VA appliance inside the wiring box is for internal
systems only.
4. Wire individual load/zone valves to their associated contacts on the secondary pump/zone
valve connector. Do not confuse such "load/zone valves" with similar valves used to
segregate a single load type (e.g., those used on a zoned radiant floor) – see the next
section.

3.13.5 Thermostat / sensor wiring

Each of the four loads has dry contacts for thermostats as marked on the lower connector strip
(e.g., "Therm 1"). Gang lines from a multiple-zoned load (e.g., off the end-switches for each radiant
floor zone) present a common thermostat signal to the controller. Ensure that there are no
disturbing influences on the call-for-heat lines - for example, that there are no coils to switch an air
handler motor. Most power stealing thermostats can be connected directly to the Therm terminals.
Consult the Controller manual for more detailed instructions.

3.13.6 Thermostat heat anticipator

IBC "Therm" contacts draw no power, so an anticipator setting for the thermostat is not applicable
with these appliances. In the case of a single temperature / heat load where zone valves are used
to manage individual thermostatically controlled zones, each room thermostat's heat anticipator
should be adjusted to the current draw of its associated zone valve.