Safety And Ignition Module (Sim+) - IBC Sl Series Installation & Operating Manual

Residential condensing boiler
Hide thumbs Also See for Sl Series:
Table of Contents

Advertisement

Check the operation of the sensor by isolating the boiler from its system piping, and close the system
fill valve, and then crack the pressure relief valve. The pressure displayed should reflect declining
pressure. If it remains "fixed", drain the boiler and replace the sensor, or dislodge any blocking debris
from the sensor inlet channel and reinsert.

8.1.4 Safety and Ignition Module (SIM+)

The SIM+ is a safety control, certified to conform to the UL 60730-5-5 and ANSI Z21.20 • CAN/CSA-
C22.2 No. 60730-2-5-14 standards.
The module controls the boiler's combustion fan, gas valve, sensors, safety and ignition functions
including:
Direct spark automatic ignition
Flame detection and current measurement
Supply water temperature sensing
Flue gas temperature sensing
Supply water maximum temperature shutdown
Flue gas maximum temperature shutdown
Low water cut-off.
The SIM+ continuously communicates with the boiler's main controller reporting sensor readings
and status. The sensor readings and error status, if any are displayed on the boiler controller's
screen.
8.1.4.1 Table showing LED operating status
Its two status LEDs indicate the operating status as shown in the table below.
LED 1
Rapid flash
Rapid flash
Off
Off
Off
On
SIM+ Status Indicators
LED 2
State
Power up or
resetting
Standby
Pre-purge or
inter-purge
91
8.1.4 Safety and Ignition Module (SIM+)
Description, LED status indication
Startup checks and initialization
LED 1 Off = No flame or sparking
LED 2 = Burner-on call state
LED 1 Off = No flame or sparking
LED 2 = Burner-on call state

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl 10-85 g3Sl 14-115 g3Sl 20-160 g3Sl 30-199 g3

Table of Contents