8.3.2 Temperature issues

Issue
Low heat
Operating temperature too low.
Increase temperature target.
Priority parameters or load
configuration improperly set up.
Appliance undersized.
Air trapped within system.
Improper system piping.
System pump undersized.
Poor gas:air mixing.
Defective thermostat.
Obstruction in condensate
drain.
Appliance cycling on operating/
safety controls.
System radiation undersized.
Temperature
Incorrect anticipator setting.
exceeds thermostat
Thermostat not level.
setting
One or more zones
Air trapped within zone(s)
do not heat properly
piping
Low radiation/ excessive heat
loss.
Low flow rate to zone(s).
Defective zone valve/ zone
circulator.
Temperature issues
Diagnosis
Increase temperature target.
Review load configuration parameters.
Refer to Load Calculation vs. Boiler
Output.
Bleed system as required.
Refer to recommended piping guidelines
for the respective boiler model.
Check pump manufacturer's data/check
temp differential across heat exchanger.
Check CO
Refer to manufacturer's instructions.
Inspect and clean condensate drain.
Check operation with
Ohmmeter/Voltmeter.
Check manufacturer's rating tables for
capacity per foot.
Check with Ammeter.
Check level.
Vent system/zone as required.
Check actual length of pipe using radiation
/ heat loss calculation.
Check temperature drop across zone.
Check operation per manufacturer's
instructions.
97
8.3.2 Temperature issues
Fix