Water Piping - IBC Sl Series Installation & Operating Manual

Residential condensing boiler
Hide thumbs Also See for Sl Series:
Table of Contents

Advertisement

3.11 Water Piping

Warning
Water quality has a significant impact on the lifetime and performance of a boiler's
heat exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat
exchanger through fouling or corrosion. Repeated or uncontrolled water fills will
increase the potential for damage.
High levels of dissolved solids or minerals may precipitate out of the fluid onto the
hottest part of the heat exchanger, impairing heat transfer and resulting in overheating
and premature failure. The amount of solids that may form on the heat exchanger will
depend on the degree of hardness and the total water volume in the system. A high
water volume system with a low hardness count may cause as much damage as a
system with less volume and higher hardness, so it is recommended to treat water so
as to remove all dissolved solids. Other water chemistry allowable limits are as
follows:
Acidity pH is to be between 6.6 and 8.5
Chloride is to be less than 125 mg/l
Iron is to be less than 0.3 mg/l
Cu less than 0.1 mg/l
Conductivity is to be less than 400μS/cm (at 77°F [25°C])
7 grains/ gal (120 ppm)
Important: Ensure that these limits are acceptable for the other water-side
components in the system.
Boiler Head Loss - SL 10-85 G3, SL 14-115 G3
Flow rate (gpm)
Head @ flow (ft wc)
Table 6
SL 10-85 G3, SL 14-115 G3 Boiler Head Loss
Flow rate (gpm)
Head @ flow (ft wc)
Table 7
SL 20-160 G3 Boiler Head Loss
2
4
6
0.5
1.5
2.5
Boiler Head Loss - SL 20-160 G3
4
6
8
0.5
1.0
1.5
42
Section: Installation
8
10
12
3.0
4.0
4.5
10
12
14
2.0
3.0
4.0
14
6.0
16
5.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl 10-85 g3Sl 14-115 g3Sl 20-160 g3Sl 30-199 g3

Table of Contents