IBC Sl Series Installation & Operating Manual page 82

Residential condensing boiler
Hide thumbs Also See for Sl Series:
Table of Contents

Advertisement

Boiler
Component
Freeze
Check the effectiveness of the glycol in the system. Use
protection
only antifreeze made specifically for hydronic systems.
Inhibited propylene glycol is recommended. Antifreeze
volume must be between 25% and 50% of the total
volume of water in the system.
Water
Check water pressure and temperature.
There should be no noticeable change if boiler is
functioning normally. Check for any noise in the system.
Check water piping for damage or leaks and repair as
Maintenance Required
Warning
Do not use automotive-type ethylene or other
types of automotive glycol antifreeze, or
undiluted antifreeze of any kind. This may
result in severe boiler damage. It is the
responsibility of the Installer to ensure that
glycol solutions are formulated to inhibit
corrosion in hydronic heating systems of
mixed materials. Improper mixtures and
chemical additives may cause damage to
ferrous and non-ferrous components as well
as non-metallic, wet components, normally
found in hydronic systems. Ethylene glycol is
toxic, and may be prohibited for use by codes
applicable to your installation location. For
environmental and toxicity reasons, IBC
recommends only using non-toxic propylene
glycol.
Caution
Installers should inquire of local water
purveyors as to the suitability of their supply
for use in hydronic heating systems.
If water quality is questionable, a local water
treatment expert must be consulted for
testing, assessment and, if required,
treatment.
Alternatively, water or hydronic fluid of known
quality can be brought to the site.
78
Section: Service and maintenance
Frequency
Check
Annually
Annually
Annually

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl 10-85 g3Sl 14-115 g3Sl 20-160 g3Sl 30-199 g3

Table of Contents