Connecting Hart - Siemens SITRANS FS230 Compact Operating Instructions

Ultrasonic flowmeters
Table of Contents

Advertisement

Connecting
4.6 Connecting industrial enclosure
5. Connect wires to terminals using wiring tool.
Note
The terminal connector is detachable
For easier access unplug the terminal connector. After connecting the wires, plug the
terminal connector back in.
– Industrial enclosure transmitter
6. Tighten cable gland.
4.6.4

Connecting HART

Note
4 to 20 mA output
It is not required to use shielded cables for the pure 4 to 20 mA current output.
Note
HART communication
It is recommended by the FieldComm Group (FCG) to use shielded cables for the HART
communication.
56
Termination of channel 1. The numbers refer to the terminal layout, see Terminal layout
(industrial enclosure) (Page 52).
Modbus
In + (B)
In - (A)
Out + (B)
Out - (A)
Functional Earth
Compact Operating Instructions, 05/2021, A5E38755607-AC