Connecting Modbus (Wall Mount) - Siemens SITRANS FS230 Compact Operating Instructions

Ultrasonic flowmeters
Table of Contents

Advertisement

4.7.4

Connecting Modbus (wall mount)

Procedure
1. Open enclosure lid.
2. Remove blind plug and fit cable gland.
3. Push cable through open gland and cable path.
4. Restore ferrule and tighten cap to hold cable in place.
5. Connect wires to terminals using wiring tool.
Note
The terminal connector is detachable
For easier access unplug the terminal connector. After connecting the wires, plug the
terminal connector back in.
– Wall mount transmitter
6. Tighten cable gland.
SITRANS FS230
Compact Operating Instructions, 05/2021, A5E38755607-AC
4.7 Connecting wall mount enclosure
Modbus
B
A
Connecting
69