Technical details

8
Technical details
General
Approvals
Application area
Module's device code
Electrical data
Supply voltage
for
Voltage
Type
Voltage tolerance
Max. continuous current that the external power
supply must provide
Inrush current that the external power supply must
provide
Supply voltage
for
Voltage
Type
Voltage tolerance
Max. continuous current that the external power
supply must provide
Potential isolation
Supply voltage
Module's current consumption
Module's power consumption
Max. power dissipation of module
Status indicator
Permitted loads
Configurable inputs/outputs (inputs or auxiliary
outputs)
Number
Potential isolation
Configurable inputs
Input voltage in accordance with EN 61131-2 Type
1
Input current at rated voltage
Input current range
Pulse suppression
Maximum input delay
Configurable auxiliary outputs
Voltage
Output current
Output current range
Max. transient pulsed current
Short circuit-proof
Residual current at "0"
Operating Manual PNOZ m B0
1002660-EN-02
772100
BG, CCC, CE, GOST, TÜV
Failsafe
0060h
772100
Supply to the system
24 V
DC
-20 %/+25 %
1,6 A
3,0 A
Supply to the SC outputs
24 V
DC
-20 %/+25 %
8,0 A
Yes
32 mA
0,8 W
7,40 W
Display, LED
Inductive, capacitive, resistive
772100
8
nein
24,0 V
5 mA
2,5 - 5,3 mA
0,5 ms
2,0 ms
24,0 V
75 mA
0 - 100 mA
500 mA
Yes
0,5 mA
30