Page 1
PNOZ mmc11p Configurable compact control systems PNOZmulti Mini Operating Manual 1002697-EN-03...
Page 2
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
General wiring guidelines Connecting the supply voltage Interface assignment Download modified project to the PNOZmulti safety system Preparing for operation Connection example Section 7 Operation Messages Section 8 Technical details Section 9 Order reference Product Accessories Operating Manual PNOZ mmc11p 1002697-EN-03...
Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ mmc11p. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Page 5
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ mmc11p 1002697-EN-03...
24 - 127 are used they have different properties (see document entitled "Communication Interfaces"). Max. 1 PNOZ mmc11p can be connected to the base unit Plug-in connection terminals: either spring-loaded terminal or screw terminal available as an accessory (see order...
Safety Safety Intended use The expansion module PNOZ mmc11p is used for communication between the configur- able control system PNOZmulti with EtherCAT. EtherCAT is designed for fast data exchange at field level. The expansion module PNOZ mmc11p is a passive EtherCAT subscriber (Slave). The basic communication functions with EtherCAT conform to the system description published by the EtherCAT User Group.
Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ mmc11p 1002697-EN-03...
PNOZmulti Configurator. The base unit and the expansion module PNOZ mmc11p are connected via a jumper. After the supply voltage is switched on or the PNOZmulti control system is reset, the expansion module PNOZ mmc11p is configured and started automatically.
NOTICE Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm Operating Manual PNOZ mmc11p 1002697-EN-03...
Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ mmc11p 1002697-EN-03...
Connect the supply voltage to the fieldbus module: 24 V terminal: + 24 VDC 0 V terminal: 0 V Protect the supply voltage as follows: – Circuit breaker, characteristic C - 6 A – Blow-out fuse, slow, 6A Operating Manual PNOZ mmc11p 1002697-EN-03...
Install the Device Description File in your configuration software. You can only then use the PNOZ mmc11p. Connect the supply voltage to the base unit: Terminals 24 V and A1 (+): + 24 VDC Terminals 0 V and A2 (-) : 0 V Operating Manual PNOZ mmc11p 1002697-EN-03...
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base unit. The expansion module PNOZ mmc11p is configured and started automatically. The LEDs "L/A 1" and "L/A 2", "Run " and "Error" indicate the status of thePNOZ mmc11p on Ether- CAT.
Vibration In accordance with the standard EN 60068-2-6 Frequency 10,0 - 150,0 Hz Acceleration Shock stress In accordance with the standard EN 60068-2-27 Acceleration Duration 11 ms Max. operating height above sea level 2000 m Operating Manual PNOZ mmc11p 1002697-EN-03...
Page 19
Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Dimensions Height 100,0 mm Width 22,5 mm Depth 115,0 mm Weight 95 g Where standards are undated, the 2012-10 latest editions shall apply. Operating Manual PNOZ mmc11p 1002697-EN-03...
Screw terminals, 10 pieces 793 543 PNOZ mmcxp 10 pcs. Terminator, jumper Product type Features Order No. PNOZ s terminator plug Terminator, yellow, 10 pieces 750 010 PNOZ s connector Jumper, 10 pieces 750 020 Operating Manual PNOZ mmc11p 1002697-EN-03...
Page 21
Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95446300 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland +41 62 88979-30 Mexico +43 1 7986263-0...