14 Advanced settings
14.5

O verhead Presence Detection (OPD) Monitoring (Level 4)

a Disconnect batteries if any.
b Disconnect the mains.
c Press the LEARN BUTTON (LRN) and keep it depressed.
d Connect the mains.
e Watch the ERROR LED.
3 s
f
Release the LEARN BUTTON after 4 flashes (LED is out).
g Identify the current monitoring
The ERROR LED flashes an amount of short flashes that correspond to the status number.
After a short pause the LED will repeat the status number and so on.
h Changing the status
If you push the LEARN BUTTON once, the status number will increase. When you have reached
the highest status number it will start at number one again.
• Push the button until you get the requested monitoring status, 1 = OFF (default), 2 = ON
• Disconnect the mains
Next time you connect the mains the operator will use the new status setting.
i
Recommended settings for sensor SP34-M
Sensor dip switch settings
Dip 1 = ON
Dip 2-8 = OFF
Interface dip switch settings
Dip 1, 4 and 7 = OFF
Dip 2, 3, 5, 6 and 8 = ON
60
1 s
3 s
1 s
Sensor
Sensor
Issue 2021-02-24
3 s
1 s
3 s
Interface
Interface
Control unit
Control unit
1005088-en-22.0