10 Electrical connection
10.2.4

Extension unit EXU-SI

Functions
This extension unit has inputs for electro-mechanical lock, program selector, batteries, KILL function, OPEN/CLOSE,
KEY opening and outer impulse.
Battery backup unit
0.5 s
0 s
3 s
ON
1
2
3
4
5
DIP-switches
shown in OFF
position
ON
1
2
3
4
5
Battery monitoring
Lock kick
Lock release
Locked without power (OFF) / with power (ON)
Lock 12 V (OFF) / 24 V (ON)
1)
Position OFF: Smooth closing, to be used on doors without lock.
Position ON: More powerful closing, to be used on doors with lock, to overcome binding in the locking device.
2)
If the switch is set to ON, the LOCK RELEASE is active during the opening delay time set by the potentiometer.
For PAIR OF DOORS installations, the LOCK RELEASE works in sequence: First the primary then the secondary.
Note! Lock only functions when Program Selector is in OFF or EXIT.
If a program selector is not used, a jumper is required from position 3 to position 11.
46
+24 V DC
OPEN
Program selector
EXIT
OFF
Unlocked signal from lock
UNL
KILL reset (see jumper below)
KRST
KILL impulse
KILL
KEY impluse (5 s)
KEY
OPEN / CLOSE impulse (latching relay)
O/C
Outer impulse
OIMP
Ground
GND
Electro-mechanical locking device (12V DC max. 500 mA /
24 V DC max 250 mA, see DIP-switch No. 1 below)
+
Potentiometer for opening delay
Automatic kill reset (jumper on)
Manual kill reset (jumper off)
1)
2)
Issue 2021-02-24
2)
1005088-en-22.0