General Technical Data - Danfoss VLT FC 103 Instruction Manual

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Specifications

10.2 General Technical Data

Line power supply
Supply Terminals
Supply voltage
Supply voltage
Supply voltage
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage
drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated
supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency
drive's lowest rated supply voltage.
Supply frequency
Max. temporary imbalance between line phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤7.5 kW
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW
Switching on input supply L1, L2, L3 (power-ups) ≥ 90 kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
Motor output (U, V, W)
Output voltage
Output frequency (1.1–90 kW)
Switching on output
Ramp times
1)
Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to FC 103's nominal torque.
Cable lengths and cross-sections for control cables
Max. motor cable length, shielded
Max. motor cable length, non-shielded
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1)
For power cables, see electrical data tables.
MG16E222
Instruction Manual
1)
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
50/60 Hz ±5%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
Near unity (> 0.98)
Maximum 2 times/min.
Maximum 1 time/min.
Maximum 1 time/2 min.
Overvoltage category III/pollution degree 2
0–100% of supply voltage
Maximum 110% for 1 min.
Maximum 135% up to 0.5 s
Maximum 110% for 1 min.
500 ft [150 m]
1,000 ft [300 m]
2
0.0023 in
[1.5 mm
0.0016 in
2
[1 mm
0.0008 in
2
[0.5 mm
0.25 mm
L1, L2, L3
0–590 Hz
Unlimited
1–3600 s
10
10
*
*
*
2
]/16 AWG
2
]/18 AWG
2
]/20 AWG
2
/24 AWG
85