Installation
2
2
1
9
Figure 2.5 Typical Electrical Connection
1
PLC
2
Adjustable frequency drive
3
Output contactor (generally not recommended)
4
Grounding rail (PE)
5
Cable insulation (stripped)
Table 2.2
NOTICE!
Use min. 0.016 in
12
2
10
L1
L2
L3
PE
8
2
[10 mm
2
] cables for optimal EMC.
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Instruction Manual
7
6
Min. 7.9 in [200 mm] between control cables, motor and line
power
7
Motor, 3-phase and PE
8
Line power, 3-phase and reinforced PE
9
Control wiring
10
Equalizing min. 0.025 in
3
4
5
6
U
V
W
PE
2
2
[16 mm
]
MG16E222