display
Defines the period between the end of defrost cycle and beginning of the next defrost cycle. A time-
description
based defrost cycle helps improve evaporator efficiency.
In the event of power loss, the defrost duration (
l
considerations
If icing up occurs, review the values of the defrost parameters.
l
range
0 to 199 hours
global default
06 hours
10.16
defrost method (dF)
The table below details the defrost method (dF) parameter.
display
description
Provides the option for a time-based or temperature-based defrost cycle.
Used only with sub zero and OFC firmware.
considerations
Not available on GDC firmware.
range
00 (time-based) or 01 (temperature-based)
global default
00 (time-based)
10.17
differential (dIF)
The table below details the differential (dI F) parameter.
display
Defines the compressor cut-in temperature when added to the set point (S PC or S PF) temperature dur-
description
ing the ready mode.
If the differential (dI F) is set too low, for example, less than 2.0°Cthe compressor may cycle on the min-
considerations
imum compressor rest time (rt).
range
0.0 to 9.9°C (0 to 18°F)
4.0°C (7°F)
global default
ems75sz: 3.0°C (5°F)
10.18
display (dIS)
The table below details the display (dI S) parameter.
display
dE
) is not maintained. The defrost interval is reset.
ems55advanced and ems55Radvanced / General Use
72 of 84