display
Enables or disables a warning buzzer for alarm conditions.
description
Door open alarms alwayssound the warning buzzer.
Following alarm conditions trigger the buzzer:
refrigeration system failure (
l
sensor failure (
l
considerations
gas cooler high temperature alarm
l
CO2 lock out alarm
l
Door alarms sound the buzzer as standard.
range
00 (disabled) or 01 (enabled)
global default
01 (enabled)
10.7
buzzer duration (b1)
The table below details the buzzer duration (b1) parameter.
display
Defines the duration of the buzzer for door open alarm conditions.
description
If the door remains open after the buzzer duration (b1), the ems controller switches off the compressor.
The ems controller switches off the compressor after the duration defined by alarm delay (Ad) + buzzer
considerations
duration (b1).
range
1 to 254 seconds
global default
60 seconds
10.8
calibration 1 (CA1)
The table below details the calibration 1 (C A1) parameter.
display
description
Calibrates or adds an offset to temperatures measured by the appliance sensor.
considerations Applied to all temperatures measured on the appliance sensor.
range
-9.9 to 9.9°C (-18 to 18°F)
global default
0.0°C (0°F)
10.9
calibration 2 (CA2)
The table below details the calibration (C A2) parameter.
ems55advanced and ems55Radvanced / General Use
69 of 84
rS F
)
PF1
PF2
PF3
,
, and
).