During the ready mode, ems controllers display appliance sensor temperature 3.0, for example or the word US E as defined
by display (dI S) parameter.
If the ems controller displays the appliance sensor temperature, the display stability (d2) parameter can dampen the rate of
change of the displayed temperature.
For example, to filter short fluctuations in the air temperature due to the door opening, which has no affect on the product
temperature.
At the end of the ready mode, ems controllers switch to the saving mode. However, the delay to saving (dS) parameter can
delay the switch to the saving mode. The delay helps ensure that, for example, the ems controller remains in the ready mode
during periods without activity immediately prior to outlets closing for marketing purposes.
For more information about the parameters used in ready mode:
See "display stability (d2)" on page 70
l
See "differential (dIF)" on page 72
l
See "display (dIS)" on page 72
l
See "delay to saving (dS)" on page 73
l
See "set point (SPC or SPF)" on page 80
l
5.4

saving mode

ems controllers run in the saving mode when retail outlets are closed.
In the saving mode, the product temperature is allowed to rise to a predefined temperature. The saving mode temperature
range is defined by saving set point (S S P) and the saving differential (S d).
The compressor runs until the saving set point (S S P) temperature is reached and then stops until the measured tem-
perature reaches the saving set point (S S P) plus saving differential (S d) temperature.
ems55advanced and ems55Radvanced / General Use
21 of 84

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ems55advanced and is the answer not in the manual?

Questions and answers

Marcilene de Almeida Ferreira
February 5, 2025

O meu aparelho está desregulado.....como colocar os números q vieram de fábrica nele

This manual is also suitable for:

Ems55radvancedEms25+Ems25advanced

Table of Contents

Save PDF