Defines whether the ems controller displays the temperature 3.0, or the word US E during the ready
mode.
description
ems controllers always display alarms.
considerations None
range
00 (US E) or 01 (temperature)
global default
01 (temperature)
10.19
delay to saving (dS)
The table below details the delay to saving (dS) parameter.
display
Defines the delay in switching to the saving mode
from ready mode.
description
The delay starts at the end of the last active 30 minute
period of the ready mode.
considerations Must be set in multiples of 30 minutes.
range
0 to 120 minutes (in multiples of 30 minutes)
global default
00 (no delay)
10.20
defrost termination temperature (dtd)
The table below details the defrost temperature duration (dtd) parameter.
display
Defines the temperature to end the defrost cycle.
Ending defrost cycles on temperature minimizes the duration of defrost cycles.
The temperature is measured as follows:
description
OFC
l
GDC
l
Must be set above the set point (
l
considerations
Must be set below
l
If icing up occurs, review the values of the defrost parameters.
l
1 to 30ºC (33 to 86ºF)
range
ems75sz: -5 to 22ºC (23 to 71ºF)
9.0ºC (48ºF)
global default
ems75sz: 15.0ºC (59ºF)
10.21
defrost termination method (dtF)
The table below details the defrost termination method (dtF) parameter.
ems55advanced and ems55Radvanced / General Use
73 of 84
and sub-zero coolers: the temperature is measured on the evaporator sensor.
coolers: the temperature is measured on the appliance sensor.
S P
) plus differential (
I Pd
.
dI F
) temperature.