PF1
alarms: ems controllers stop running the compressor and then waits 60 seconds before re-starting (switch off and then switch on).
l
If the fault continues, the ems controller repeats and continues the cycle until the fault corrected.
PF2
alarms: ems controllers continue running the compressor.
l
ems controllers alternate the display between
indicating a fault.
PF2
alarms: ems55advanced CO2 controllers continue to run the compressor normally and alternate the display
l
sensor temperature indicating a fault.
PF3
alarms: ems controllers continue to run the compressor normally and alternate the display
l
perature.
Sensor faults may also be identified by using the input test within the test routine:
See "how to run the test routine (tst)" on page 40
l
Follow the chart to troubleshoot problems with the appliance sensor, condenser sensor, evaporator sensor or gas cooler
sensor.
8.8
how to troubleshoot problems with freeze-up protection (888)
Problems with freeze-up protection may occur if the ambient temperature falls below 0°C (32°F) or if the appliance sensor
fails.
ems55advanced and ems55Radvanced / General Use
51 of 84
PF2
and the appliance sensor temperature
PF2
and the gas cooler
PF3
and the appliance sensor tem-