How To Troubleshoot Problems With Freeze-Up Protection (888) - Elstat ems55advanced Manual

Hide thumbs Also See for ems55advanced:
Table of Contents

Advertisement

PF1
alarms: ems controllers stop running the compressor and then waits 60 seconds before re-starting (switch off and then switch on).
l
If the fault continues, the ems controller repeats and continues the cycle until the fault corrected.
PF2
alarms: ems controllers continue running the compressor.
l
ems controllers alternate the display between
indicating a fault.
PF2
alarms: ems55advanced CO2 controllers continue to run the compressor normally and alternate the display
l
sensor temperature indicating a fault.
PF3
alarms: ems controllers continue to run the compressor normally and alternate the display
l
perature.
Sensor faults may also be identified by using the input test within the test routine:
See "how to run the test routine (tst)" on page 40
l
Follow the chart to troubleshoot problems with the appliance sensor, condenser sensor, evaporator sensor or gas cooler
sensor.
8.8

how to troubleshoot problems with freeze-up protection (888)

Problems with freeze-up protection may occur if the ambient temperature falls below 0°C (32°F) or if the appliance sensor
fails.
ems55advanced and ems55Radvanced / General Use
51 of 84
PF2
and the appliance sensor temperature
PF2
and the gas cooler
PF3
and the appliance sensor tem-

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ems55advanced and is the answer not in the manual?

Questions and answers

Marcilene de Almeida Ferreira
February 5, 2025

O meu aparelho está desregulado.....como colocar os números q vieram de fábrica nele

This manual is also suitable for:

Ems55radvancedEms25+Ems25advanced

Table of Contents

Save PDF