This message is for the use case when an implementation has detected an Over-Temperature Condition
Detected for Processor.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0036
User Action:
Complete the following steps until the problem is solved:
1. Check xClarity Controller (XCC) event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers/airduct
are in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the microprocessor 1 heat sink is securely installed.
5. Make sure that the microprocessor 1 heat sink is installed correctly and the thermal material is
correctly applied.
6. Contact service for further support
• FQXSPPU0002G: The Processor [ProcessorElementName] is operating in a Degraded State.
This message is for the use case when an implementation has detected a Processor is running in the
Degraded state.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - CPU
SNMP Trap ID: 42
CIM Prefix: PLAT CIM ID: 0038
User Action:
Complete the following steps until the problem is solved:
1. Check xClarity Controller (XCC) event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers/airduct
are in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the microprocessor 1 heat sink is securely installed.
5. Make sure that the microprocessor 1 heat sink is installed correctly and the thermal material is
correctly applied.
6. Contact service for further support
• FQXSPPU0007N: CPU voltage mismatch detected on [ProcessorElementName].
This message is for the use case when an implementation has detected a CPU voltage mismatch with the
socket voltage.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - CPU
82