AHF 005/010 Operating Instructions
380 - 415 V
50 Hz
I
Contactor Rating
AHF,N
KVAr
10 A
2
19 A
4
26 A
6
35 A
7
43 A
9
72 A
15
101 A
22
144 A
29
180 A
37
217 A
44
289 A
58
324 A
66
370 A
73
NB!
Only switch the contactor at less than 20% output power. Allow minimum 240 seconds for the capacitors to discharge before turning
on again.
Use cables complying with local regulations.

4.1.5 Fuses

In order to protect the installation against electrical and fire hazards, all filters in an installation must be short-circuited and over-current protected
according to national/international regulations. The filter must be protected against short-circuit and overload to avoid electrical or fire hazard and to
protect cables and filter from overheating. Danfoss recommends using fuses mentioned below to protect service personnel and equipment in case of an
internal failure in the filter.
380 - 415 V
440 - 480 V
60 Hz
60 Hz
Contactor Rating
Contactor Rating
KVAr
KVAr
5
5
7
7
9
10
11
12
18
20
26
27
35
39
44
51
53
69
70
78
79
87
88
99
®
MG.80.C1.02 - VLT
is a registered Danfoss trademark
500 - 525 V
690 V
50 Hz
50 Hz
Contactor Rating
Contactor Rating
KVAr
KVAr
2
4
6
8
11
16
18
27
25
34
35
50
46
61
53
79
74
101
85
121
135
4 Installation
4
21