AHF 005/010 Operating Instructions
I
AHF,N
[Amp]
43
72
101
144
180
217
289
324
370
Table 4.5: AHF005 and AHF010, 690V, 50Hz

4.1.6 Over temperature contactor

The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvanic isolated contactor that is closed under normal operating conditions
and open if the filter is overheated. A controlled ramp down within 30 s is allowed with overheat damage of filter. This contactor must be used to
prevent damage to the filter caused by over temperature as shown in the following example.
NB!
The maximum rating of the over temperature contactor is 250V AC and 10A.

4.1.7 Power wiring size

Enclosure
Max. cable size mm
B
C and D
E, F, G and H
Table 4.6: Power wiring size
Enclosure
Max. cable size mm
Table 4.7: Overheat contactor (copper)
Enclosure
Max. cable size mm
B
C and D
E, F, G and H
Table 4.8: Capacitor disconnect (copper)
*Power wiring used for connection of the filter AHF 005 and AHF 010 in enclosure size E, F and G must be terminated with cable lugs that can be attached
to the input and output bus bars terminals. This type of termination imposes no specifications of the minimum and maximum cable size suitable for
connection. Power terminal details regarding the bus bars can be found in the figures below.
ordering number
max fuse rating
AHF 005
[Amp]
130B2328
130B2330
130B2331
130B2333
130B2334
130B2335
AWG
2
16
50
*
2
AWG
4
2
AWG
4
16
50
®
MG.80.C1.02 - VLT
is a registered Danfoss trademark
ordering number
AHF 010
63
130B2293
125
130B2295
160
130B2296
250
130B2298
315
130B2299
315
130B2300
130B2301
130B2302
130B2304
Example: Connect terminal A of the harmonic filter to terminal 12 or13
(voltage supply digital input, 24V) of the Danfoss frequency converter and
terminal B to terminal 27 (digital input "Coast Inverse") the frequency
converter will let go of the motor (coasting) and thereby unload the filter
if an over temperature is detected.
Type
6
Connector
1
Connector
*
Bus Bars
Type
Connector
Type
10
Connector
6
Connector
1
Connector
4 Installation
max fuse rating
[Amp]
63
125
160
250
315
315
500
500
630
4
Nom. Fix Torque
2 Nm
6 Nm
25 Nm
Nom. Fix Torque
0.6 Nm
Nom. Fix Torque
0.6 Nm
2 Nm
6 Nm