3. Shielded output cables (motor cables) and connect the shield at both ends (motor and
inverter) with a low impedance connection for high frequency. Use PCSx-01 kit supplied
with frame sizes A, B and C inverters. For frame sizes B and C with degree of protection
IP55, use the PCSC-03 shield kit. For frame sizes D and E inverters use the clamps supplied
with the product. Ensure good contact between the cable shield and the clamps. Refer to
Figure 3.4 on page 18
Item 3.2.6 Cable Distances on page
and radiated emission levels are presented at
filter at the input of the inverter if necessary to have a lower emission level and/or a longer
motor cable length. For more information (RFI filter commercial reference, motor cable
length and emission levels) refer to
4. Shielded control cables and separate the remaining cables according to
Distances on page
5. Inverter grounding according to the instructions on
page
18.
6. Grounded power supply.

3.3.2 Emission and Immunity Levels

EMC Phenomenon
Emission:
Mains Terminal Disturbance Voltage
Frequency Range: 150 kHz to 30 MHz).
Electromagnetic Radiation Disturbance
Frequency Range: 30 MHz to 1000
MHz).
Immunity:
Electrostatic Discharge (ESD).
Fast Transient-Burst.
Conducted Radio-Frequency Common
Mode.
Surge Immunity.
Radio-Frequency Electromagnetic
Field.
Refer to
Table B.7 on page 168
with and without external RFI filter. The reference model for the external filter is also presented.
and keep the proper separation from other cables according to
22. The maximum motor cable length and conduction
Table B.7 on page
22.
Table 3.3: Emission and immunity levels
Basic
Standard
IEC/EN61800-3
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-6
IEC 61000-4-5
IEC 61000-4-3
for conducted and radiated emission levels accomplished
Installation and Connection
Table B.7 on page
168. Use an external RFI
168.
Item 3.2.4 Grounding Connections on
Level
It depends on the inverter model and the
motor cable length.
See
Table B.6 on page
4 kV for contact discharge and 8 kV for air
discharge.
2 kV / 5 kHz (coupling capacitor) power input
cables.
1 kV / 5 kHz control cables, and remote
keypad cables.
2 kV / 5 kHz (coupling capacitor) motor
output cables.
0.15 to 80 MHz; 10 V; 80 % AM (1 kHz).
Power supply cable, motor, control and
remote keypad (HMI).
1.2/50 μs, 8/20 μs.
1 kV line-to-line coupling.
2 kV line-to-ground coupling.
80 to 1000 MHz.
10 V/m.
80 % AM (1 kHz).
Item 3.2.6 Cable
165.