Bosch Rexroth IndraDrive X Operating Instructions Manual page 76

Table of Contents

Advertisement

60/123
Mounting, dismounting and electrical installation
Arranging components and lines
Control voltage or auxiliary voltage
connection
Line routing
Influence of the motor power cable
Routing the motor power cables
and motor encoder cables
Routing the motor power cables
and mains connection lines
Bosch Rexroth AG R911392532_Edition 01
IndraDrive X Drive Controllers Power Sections XCS1, XMD1,
equipment grounding conductor using separate terminals (according to EN
61800-5-1:2007+A1:2017, section 4.3.5.5.2). If the cross section of the outer
conductor is bigger, the cross section of the equipment grounding conductor
has to be accordingly bigger.
Design and installation in area B - control cabinet area prone to inter‐
ference
Modules, components and lines in area B have to be placed at a distance of
at least d1 = 200 mm from modules and lines in area A.
Alternative: Shield modules, components and lines in area B using distance
plates mounted vertically on the mounting plate from modules and lines in
area A or use shielded lines.
Only connect power supply units for auxiliary or control voltage connections
in the drive system to the mains via a mains filter. See
(zones), page
55.
Install the shortest possible lines between drive controller and filter.
Only in exceptional cases should you connect power supply unit and fusing
for the control voltage connection to phase and neutral conductor. In this
case, mount and install these components in area A far away from the
areas B and C of the drive system. For details see section
installation in area A - control cabinet area free from interference, page
Run the connection between the control voltage connection of the drive
system and the power supply unit used through area B over the shortest
distance.
Run the lines along grounded metal surfaces, in order to minimize radiation
of interference fields to area A (transmitting antenna effect).
Design and installation in area C - control cabinet area highly prone to
interference
Area C mainly concerns the motor power cables, especially at the connection
point at the drive controller.
The longer the motor power cable, the greater its leakage capacitance. To
comply with a certain EMC limit value, the allowed leakage capacitance of
the mains filter is limited. For the calculation of the leakage capacitance, see
the documentation on the drive system of the drive controller used.
Run the shortest possible motor power cables.
Only use shielded motor power cables by Rexroth.
Route the motor power cables and motor encoder cables along grounded
metal surfaces, both inside the control cabinet and outside of it, in order to
minimize radiation of interference fields. If possible, route the motor power
cables and motor encoder cables in metal-grounded cable ducts.
Route the motor power cables and motor encoder cables
with a distance of at least d5 = 100 mm to interference-free lines, as
well as to signal cables and signal lines
(alternatively separated by a grounded distance plate)
in separate cable ducts, if possible
For converters (drive controllers with individual mains connection), route
motor power cables and (unfiltered) mains connection lines parallel to one
another for a maximum distance of 300 mm. After that distance, route motor
XMQ1
Division into areas
Design and
58.