Arranging the cooling units

Avoiding dripping or spraying wa‐
Bosch Rexroth AG R911392532_Edition 01
1
Discharge of heated air to cooling unit
2
Interior of control cabinet
3
Conveying direction of heated air in area where air flows off
4
Device in control cabinet
5
Air intake at device
6
Air guide in control cabinet (for liquid cooling, this is also the
drip protection for the devices beneath)
7
Fan in control cabinet
8
Supply of cooled air from cooling unit
Fig. 10-2:
Examplary arrangement of double-line design
Unless the nominal data are reduced, the drive controller may only be
operated up to a specified maximum ambient temperature. A cooling unit
might therefore be required.
NOTICE
Observe the instructions below.
Due to their operating principle, condensation water is formed when cooling
ter
units are used.
For this reason, observe the following aspects:
Always position cooling units in such a way that condensation water
cannot drip onto the devices in the control cabinet.
IndraDrive X Drive Controllers Power Sections XCS1, XMD1,
Possible damage to the drive controller!
Operational
safety
endangered!
XMQ1
of
the
machine