Nuvation Energy Low-Voltage BMS - Product Manual
for indoor use.
The Low-Voltage BMS should be securely mounted in a vertical orientation, with the label facing out.
The Battery Cells and Temperature Sensor connector should be facing up or to the left. If this is to be
used with a battery chemistry such as lead-acid—which does not require balancing—the Low-Voltage
BMS may be mounted horizontally, with the ventilation slots oriented upwards.
It is not advisable to mount the Low-Voltage BMS on the underside of a horizontal surface.
4.1.2.1. Mounting Clearances
Extra space should be provided around the module to allow for sufficient heat dissipation as well as
easy installation and maintenance. The Low-Voltage BMS - 12 channel and Low-Voltage BMS - 16
channel variants produce up to 24 W and 32 W, respectively, during cell balancing.

4.1.3. Mounting Instructions

The Low-Voltage BMS has 2 flanges with 2 clearance holes for #10-32 fasteners and 1 slot on each
flange for mounting purposes. Ensure appropriate fasteners (not included) for are used to mount the
Low-Voltage BMS. These fasteners will vary depending on the material and construction of the
mounting surface.
Document ID: NE-PM-002
10
Rev 1.2, 2021-03-03
Curie Update 1