5.5. Import the Configuration File

Once you have exported your configuration file to the computer connected to Nuvation Energy BMS,
you can proceed to import it to Nuvation Energy BMS.
To import a configuration file Nuvation Energy BMS must be in Service Lockout. Please see
6.5
for more details.
1. Ensure you are in Service Lockout
2. Ensure Persist Configuration to BMS is checked
Enabling this option tells Nuvation Energy BMS to persist the imported
configuration file. If you are using known, good, configuration files you should
check this box.
Disabling this option tells Nuvation Energy BMS to not persist the newly imported
configuration file. On reboot, Nuvation Energy BMS will revert to the previous
configuration file. This is useful when tweaking and testing configuration files. It
allows you to recover from incorrect configuration settings by rebooting Nuvation
Energy BMS
3. Click Import Configuration
4. Select the configuration file to use and click Open
5. A dialog indicating progress will pop-up
6. Wait until a dialog box appears with the configuration import result. It should indicate that the
import was successful.
Document ID: NE-PM-002