Appendix C: Changing the Nuvation Energy BMS
Network Configuration
Nuvation Energy BMS is flexible and allows changing its network configuration if you need the IP
address of Nuvation Energy BMS to match your existing network settings.
Improperly modifying the network settings can result in a Nuvation Energy BMS that
cannot communicate over Ethernet.
To restore Nuvation Energy BMS to its default IP address (192.168.1.21), you must
initiate a factory reset action—refer to the
Be sure to record the updated IP address, netmask, and gateway settings if you
decide to make changes to these settings.

Modifying the Network Settings

1. Unlock the Operator Interface by clicking the menu and Unlock
You will need the Operator Interface password if the Operator Interface is password-protected
2. From the menu, select Registers to bring up the register browser page
3. Under the Manual Register Configuration panel, expand the row for Component Name sc_ethernet.
The sc_ethernet component contains network settings like IP address, gateway, etc.
Use the find feature (Ctrl + F) in your browser to locate components in the page.
4. Click the Edit button on the register you need to modify to meet your desired network
configuration. This will bring up the Edit Register dialog box
5. Enter the desired value for the register. Then click Write
The index field may be left blank for all operations.
6. Confirm that the value has been updated by clicking Read
Document ID: NE-PM-002
Nuvation Energy Low-Voltage BMS - Product Manual
Appendix D
for instructions.
177
Rev 1.2, 2021-03-03
Curie Update 1