Accessing Mesa Models - Nuvation Energy NUV300-BC-12 Product Manual

Low-voltage bms
Table of Contents

Advertisement

Model
Block
Point Name
803
Fixed
BMinCellVolLoc
803
Fixed
BMaxModTmp
803
Fixed
BMaxModTmpLoc
803
Fixed
BMinModTmp
803
Fixed
BMaxModTmpLoc
803
Fixed
BTotDCCur
803
Fixed
BMaxStrCur
803
Fixed
BMinStrCur
803
Repeat
StrSoC
803
Repeat
StrSoH
803
Repeat
StrCur
803
Repeat
StrMaxCellVol
803
Repeat
StrMinCellVol
803
Repeat
StrCellVolLoc
803
Repeat
StrMaxModTmp
803
Repeat
StrMinModTemp
803
Repeat
StrModTmpLoc
803
Repeat
StrEvt1
The term Index in the Repeating block addresses used in the above table refers to a
calculation of Index = Stack Index * Length of Repeating block. By definition, the 803
Repeating block is 16 Modbus registers in length.

8.1.6. Accessing MESA Models

MESA models are located contiguously in the Modbus address space starting at a base address of
40000. The Common Model is always located first in this space. The End Model is always last and is
used to denote the end of MESA Modbus registers. Each model located between the Common Model
and the End Model has a numeric identifier as well as a length. A handy tool that can be used to
explore the MESA Modbus registers for Nuvation Energy BMS is modpoll.exe. It is available for free
download at http://www.modbusdriver.com/modpoll.html.
Using modpoll.exe, the Common Model can be polled from a using the following command (assuming
the device has an IP address of 192.168.1.21)
Document ID: NE-PM-002
Nuvation Energy Low-Voltage BMS - Product Manual
Address
Scale
Factor
40122
No
40123
Yes
40124
No
40125
Yes
40126
No
40127
Yes
40128
Yes
40129
Yes
40135 +Index
No
40136 +Index
Yes
40137 +Index
Yes
40138 +Index
Yes
40139 +Index
Yes
40140 +Index
No
40141 +Index
Yes
40142 +Index
Yes
40143 +Index
No
40144 +Index
No
143
Purpose
Module/String location of minimum cell voltage
Maximum module temperature
Module/String location for maximum module
temperature
Minimum module temperature
Module/String location for minimum module
temperature
Total DC current of the battery system
Largest DC current reported by a stack/string
Smallest DC current reported by a stack/string
State of charge for a stack/string
State of health for a stack/string
Current of a stack/string
Maximum cell voltage of a stack/string
Minimum cell voltage of a stack/string
Location of min/max cell voltages of a stack/string
Maximum module temperature of a stack/string
Minimum module temperature of a stack/string
Location of min/max module temperatures of a
stack/string
Alarms warnings and status bit field of a stack/string
Rev 1.2, 2021-03-03