Environmental Conditions; Standards And Certifications - Nuvation Energy NUV300-BC-12 Product Manual

Low-voltage bms
Table of Contents

Advertisement

While Low-Voltage BMS is designed for an input voltage of 11–60 V DC, testing has
confirmed that the unit experiences no degradation when using an input voltage up
to 68 V DC. However, for applications that exceed 60 V DC, please consider Nuvation
Energy High-Voltage BMS or contact support@nuvationenergy.com.
The +VPOWER input current depending on the loads the Low-Voltage BMS is driving.
Without contactors, the Low-Voltage BMS draws approximately 70 mA at 48 V DC.
With all contactors connected and energized, it can draw up to 1.25 A at 48 V DC.
Nuvation Energy BMS does not include an internal free-wheeling protection diode on
contactor coil-driver circuits, as it has been found to cause premature contactor
failure.

Environmental Conditions

Symbol
Parameter
Operating Temperature
Ta
Storage Temperature
Operational RH
RH
Storage RH
Vertical
Vertical shock/vibration
Longitudinal
Longitudinal shock/vibration
Transverse
Transverse shock/vibration
Pulse vibration
On each axis
The Low-Voltage BMS has been designed to meet the requirements of SAE J2464 (shock) and SAE
J2380 (random vibration).

Standards and Certifications

The Low-Voltage BMS is designed to comply with industry EMC standards for FCC and IC Class A, and
European EN55032 Class A. It is designed for EMI and ESD performance to EN55024, including the
IEC/EN 61000-4-X series of tests. All components are EU RoHS / China RoHS compliant.
Standard/Certification
Stationary Battery Safety
Functional Safety
UL 1973 recognition ensures safe battery operation and significantly reduce the effort of certifying the
energy storage solution to meet UL 1973 and UL 9540.
Document ID: NE-PM-002
Thermal Specifications
Humidity Specifications
Shock and Vibration Specifications
UL Recognized
UL Recognized
173
Nuvation Energy Low-Voltage BMS - Product Manual
Min
-40
-40
5
5
-
-
-
-
UL 1973 (file no. MH64071)
UL 991 (file no. MH64071)
UL 1998 (file no. MH64071)
Typ
Max
Units
25
50
°C
25
50
°C
-
85
%
-
85
%
-
10
m/s
-
10
m/s
-
10
m/s
-
245
m/s
Rev 1.2, 2021-03-03
Curie Update 1
2
2
2
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nuv300-bc-16Nuv100-ci-12-1Nuv100-ci-16-1

Table of Contents