6.3.2.1. Importing a Configuration File
This is a restricted option requiring the Operator Interface to be unlocked to access
this option.
This menu option allows you to import a configuration file.
If you have a configuration file ready to import, refer to
If you need to generate a configuration file, refer to
6.3.2.2. Exporting a Configuration File
Nuvation Energy BMS does not preserve the originally imported configuration file
with comments and formatting. The export feature will export a configuration file
with an alphabetical listing of all registers and their set values.
To export your configuration file:
1. From the menu, select Service
2. Click Export Configuration
6.3.2.3. Upgrade
This is restricted option requiring the Operator Interface to be unlocked to access
this option.
Refer to
Section 5.3
for instructions on performing a firmware upgrade.
The firmware upgrade will erase the configuration file on your Nuvation Energy BMS.
Please remember to export and save your current configuration file to save your
current configuration file for future reference.

6.3.3. Connection

The connection screen allows you to change the IP address and timeout of the Nuvation Energy BMS
that you are trying to access.
If you are connecting to a Nuvation Energy BMS that does not use the default IP address
(192.168.1.21), you will need to change the connection settings in the Operator Interface to match
the BMS:
1. Re-open the Nuvation-Energy-Operator-Interface.html file in your web browser
2. Wait for the connection message to time out
Document ID: NE-PM-002
Nuvation Energy Low-Voltage BMS - Product Manual
Section 5.5
for instructions.
Section 5.4
for instructions.