General Purpose Digital Outputs - Nuvation Energy NUV300-BC-12 Product Manual

Low-voltage bms
Table of Contents

Advertisement

stack_contactor[n].direction
Set to 0 for a non-directional contactor that breaks any current
Set to 1 for a directional contactor that breaks charge current
Set to 2 for a directional contactor that breaks discharge current
stack_contactor[n].delay
Time to wait before opening the contactor in the non-preferred direction
When directional contactors are used, set this delay to a minimum of 1 second, otherwise set
the delay to 0 seconds
stack_contactor[n].installed
Set to 1 to indicate a contactor is physically wired into the BMS
Only installed contactors will flag hardware failures via the stack_contactor[n].coil_error or
stack_contactor[n].feedback_error
stack_contactor[n].feedback_enable
Set to 1 to enable contactor feedback from a configured input
State mismatches between stack_contactor[n].feedback_value and stack_contactor[n].value will
result in stack_contactor[n].feedback_error being set to 1
For advanced applications, contactor outputs may be configured to be driven from any Boolean
register within Nuvation Energy BMS.

7.7.2. General Purpose Digital Outputs

The most commonly used General Purpose Digital Output functions are:
Charge current disable: A control signal that is asserted when charging should be disabled
Discharge current disable: A control signal that is asserted when discharging should be
disabled
Fault state: A signal that is asserted when faults are present within the system
Trigger state: A trigger signal for external devices that is asserted when a specific trigger within
the system is tripped
General Purpose Digital Output functions are assigned through the following configuration registers.
The index n is the zero-based index of the General Purpose Digital Output hardware pin.
sc_gpo[n].address_enabled
Set this to 1 to enable the function specified in sc_gpo[n].address
sc_gpo[n].inverted
When set to 0, GPO output switch is closed when assigned function value is 0
When set to 1, GPO output switch is closed when assigned function value is 1
Document ID: NE-PM-002
Nuvation Energy Low-Voltage BMS - Product Manual
113
Rev 1.2, 2021-03-03