Ametek AN-3100D Installation And Configuration Manual page 93

Table of Contents

Advertisement

or critical horn condition.
Internal Horn Silence (option AS)
The internal horn (option HN) may be automatically silenced after a fixed time.
To do this use the up and down arrows to the right of the value box to set the
required time. The maximum value is 240s and the resolution is 1.0s.
Note: A setting of 0 indicates that the auto-silence is not activated.
External Horn Silence (Option AS)
This will silence any external horn if selected for CSM Relay #1-4 in the time
increment selected. This will automatically silence the Critical, Non-Critical or
Ringback Horn when this option is included with the system. The maximum
value is 240s and the resolution is 1.0s.
Note: A setting of 0 indicates that the auto-silence is not activated.
Auto Reset
This will activate the Reset function continuously, eliminating the need to
manually press this. (Note: this only applies to alarm sequences that require the
reset function.)
Critical Audible has no affect on non-critical
This will make the operation of the non-critical horn independent of the critical
horn. See the previous section on the operation of the non-critical audible.
Critical Audible Pulsed
This will pulse the critical audible output upon an alarm.
Non-critical Audible Pulsed
This will pulse the non-critical audible output upon an alarm.
Ringback Audible Pulsed
This will pulse the ringback audible output upon an alarm.
AN-3100D ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL